Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Dayton
Assessment Year 1989
Principal Product STRIPS & SHEETS OF STEEL
NAICS n/a
SIC 3499 - Fabricated Metal Products, Nec
Sales $10,000,000-$50,000,000
# of Employees 24
Plant Area (Sq.Ft.) 0
Annual Production 47,525 Pounds
Production Hrs. Annual 4,080
Location (State) OH
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $93,000 1,500,000 kWh $0.06
Natural Gas $177,000 44,250 MMBtu $4.00
TOTAL ENERGY COSTS $270,000
RECOMMENDED SAVINGS* $204,673 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $155,620
#|Description Savings
Cost
Status Electricity Usage Natural Gas Administrative Changes Electricity Usage Natural Gas Administrative Changes
$ kWh $ MMBtu $ $
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$6,690
Cost:
-
$5,554 92,321 $(-784) (-196) $1,920 - $5,554
92,321
kWh
$(-784)
(-196)
MMBtu
$1,920
-
$
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$14,354
Cost:
-
$13,416 264,068 $(-2,252) (-563) $3,190 - $13,416
264,068
kWh
$(-2,252)
(-563)
MMBtu
$3,190
-
$
03: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE Savings:
$543
Cost:
-
$543 7,620 - - - - $543
7,620
kWh
-
-
MMBtu
-
-
$
04: 2.5196 USE SMALL NUMBER OF HIGH OUTPUT UNITS INSTEAD OF MANY SMALL INEFFICIENT UNITS Savings:
$1,105
Cost:
$6,000
$1,105 15,826 - - - - $1,105
15,826
kWh
-
-
MMBtu
-
-
$
05: 2.3212 OPTIMIZE PLANT POWER FACTOR Savings:
$6,809
Cost:
$12,000
$6,809 - - - - - $6,809
-
kWh
-
-
MMBtu
-
-
$
06: 2.7492 USE PROPER THICKNESS OF INSULATION ON BUILDING ENVELOPE Savings:
$117,912
Cost:
$60,000
- - $117,912 29,478 - - -
-
kWh
$117,912
29,478
MMBtu
-
-
$
07: 2.7494 INSTALL STORM WINDOWS AND DOORS Savings:
$47,948
Cost:
$47,000
- - $47,948 11,987 - - -
-
kWh
$47,948
11,987
MMBtu
-
-
$
08: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS Savings:
$9,312
Cost:
-
- - $9,312 2,328 - - -
-
kWh
$9,312
2,328
MMBtu
-
-
$
TOTAL RECOMMENDED Savings:
$204,673
Cost:
$125,000
$27,427 379,835 $172,136 43,034 $5,110 - $27,427
379,835
kWh
$172,136
43,034
MMBtu
$5,110
-
$
TOTAL IMPLEMENTED Savings:
$155,620
Cost:
$72,000
$26,322 364,009 $124,188 31,047 $5,110 - $26,322
364,009
kWh
$124,188
31,047
MMBtu
$5,110
-
$
Savings
Cost
$ kWh $ MMBtu $ $
Electricity Usage Natural Gas Administrative Changes Electricity Usage Natural Gas Administrative Changes