Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Dayton |
---|---|
Assessment Year | 2009 |
Principal Product | Sensors and Instruments |
NAICS | 334417 - Electronic Connector Manufacturing |
SIC | 3674 - Semiconductors And Related Devices |
Sales | $10,000,000-$50,000,000 |
# of Employees | 103 |
Plant Area (Sq.Ft.) | 65,000 |
Annual Production | 20,000 Pieces |
Production Hrs. Annual | 3,570 |
Location (State) | OH |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $91,407 | 1,927,560 | kWh | $0.05 |
Electricity Demand | $40,706 | 339 | kW-months/year | $120.08 |
Natural Gas | $43,326 | 3,589 | MMBtu | $12.07 |
TOTAL ENERGY COSTS | $181,499 | |||
RECOMMENDED SAVINGS* | $41,070 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $39,921 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7311 VENTILATION SYSTEM TO SHUT OFF WHEN ROOM IS NOT IN USE |
Savings: $18,742 Cost: $14,833 |
$2,351 | 61,891 | - | - | $16,391 | 1,358 | - | - |
$2,351 61,891 kWh |
- - kW-months/year |
$16,391 1,358 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7314 REDUCE VENTILATION AIR |
Savings: $10,610 Cost: $14,833 |
$3,918 | 52,788 | - | - | $6,692 | 554 | - | - |
$3,918 52,788 kWh |
- - kW-months/year |
$6,692 554 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7226 USE COMPUTER PROGRAMS TO OPTIMIZE HVAC PERFORMANCE |
Savings: $4,599 Cost: $14,833 |
- | - | - | - | $4,599 | 381 | - | - |
- - kWh |
- - kW-months/year |
$4,599 381 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $3,877 Cost: $16,721 |
$1,593 | 63,711 | $1,979 | 17 | - | - | $305 | - |
$1,593 63,711 kWh |
$1,979 17 kW-months/year |
- - MMBtu |
$305 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7241 INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT |
Savings: $1,100 Cost: $14,833 |
$1,100 | 15,953 | - | - | - | - | - | - |
$1,100 15,953 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4226 USE / PURCHASE OPTIMUM SIZED COMPRESSOR |
Savings: $1,087 Cost: - |
$612 | 24,480 | $475 | 4 | - | - | - | - |
$612 24,480 kWh |
$475 4 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7121 UTILIZE DAYLIGHT WHENEVER POSSIBLE IN LIEU OF ARTIFICIAL LIGHT |
Savings: $993 Cost: $45,000 |
$993 | 39,726 | - | - | - | - | - | - |
$993 39,726 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $62 Cost: - |
$35 | 1,408 | $27 | 1 | - | - | - | - |
$35 1,408 kWh |
$27 1 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $41,070 Cost: $121,053 |
$10,602 | 259,957 | $2,481 | 22 | $27,682 | 2,293 | $305 | - | $10,602 259,957 kWh |
$2,481 22 kW-months/year |
$27,682 2,293 MMBtu |
$305 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $39,921 Cost: $121,053 |
$9,955 | 234,069 | $1,979 | 17 | $27,682 | 2,293 | $305 | - | $9,955 234,069 kWh |
$1,979 17 kW-months/year |
$27,682 2,293 MMBtu |
$305 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes |