Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Dayton |
---|---|
Assessment Year | 2010 |
Principal Product | Medical Surgical Tools |
NAICS | 339112 - Surgical and Medical Instrument Manufacturing |
SIC | 3841 - Surgical And Medical Instruments |
Sales | $10,000,000-$50,000,000 |
# of Employees | 561 |
Plant Area (Sq.Ft.) | 69,250 |
Annual Production | 15,989,823 Units |
Production Hrs. Annual | 6,600 |
Location (State) | OH |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $1,002,899 | 15,250,715 | kWh | $0.07 |
Natural Gas | $25,935 | 2,128 | MMBtu | $12.19 |
TOTAL ENERGY COSTS | $1,028,834 | |||
RECOMMENDED SAVINGS* | $87,105 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $74,756 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY |
Savings: $4,575 Cost: $300,000 |
$4,575 | 59,417 | - | - | - | - | - | - |
$4,575 59,417 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $3,610 Cost: $25 |
$610 | 16,500 | $3,000 | 15 | - | - | - | - |
$610 16,500 kWh |
$3,000 15 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $3,331 Cost: $75 |
$1,831 | 49,500 | $1,500 | 8 | - | - | - | - |
$1,831 49,500 kWh |
$1,500 8 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $40,341 Cost: $60,300 |
$20,791 | 557,410 | $16,884 | 84 | - | - | $2,666 | - |
$20,791 557,410 kWh |
$16,884 84 kW-months/year |
- - MMBtu |
$2,666 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $479 Cost: $893 |
$266 | 7,128 | $216 | 1 | - | - | $(-3) | - |
$266 7,128 kWh |
$216 1 kW-months/year |
- - MMBtu |
$(-3) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $3,023 Cost: $4,000 |
- | - | - | - | $3,023 | 248 | - | - |
- - kWh |
- - kW-months/year |
$3,023 248 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $2,766 Cost: $25 |
$1,526 | 40,920 | $1,240 | 6 | - | - | - | - |
$1,526 40,920 kWh |
$1,240 6 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL |
Savings: $23,979 Cost: $43,700 |
$23,979 | 642,872 | - | - | - | - | - | - |
$23,979 642,872 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7235 INSTALL FOSSIL FUEL MAKE-UP AIR UNIT |
Savings: $2,560 Cost: $5,542 |
- | - | - | - | $2,560 | 210 | - | - |
- - kWh |
- - kW-months/year |
$2,560 210 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7224 REDUCE SPACE CONDITIONING DURING NON-WORKING HOURS |
Savings: $1,772 Cost: $3,500 |
$297 | 7,963 | - | - | $1,475 | 121 | - | - |
$297 7,963 kWh |
- - kW-months/year |
$1,475 121 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.7241 INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT |
Savings: $669 Cost: $400 |
- | - | - | - | $669 | 55 | - | - |
- - kWh |
- - kW-months/year |
$669 55 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $87,105 Cost: $418,460 |
$53,875 | 1,381,710 | $22,840 | 114 | $7,727 | 634 | $2,663 | - | $53,875 1,381,710 kWh |
$22,840 114 kW-months/year |
$7,727 634 MMBtu |
$2,663 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $74,756 Cost: $408,418 |
$50,518 | 1,291,290 | $20,100 | 100 | $1,475 | 121 | $2,663 | - | $50,518 1,291,290 kWh |
$20,100 100 kW-months/year |
$1,475 121 MMBtu |
$2,663 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes |