Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Dayton
Assessment Year 2012
Principal Product Steel and iron casting
NAICS 331513 - Steel Foundries (except Investment)
SIC 3325 - Steel Foundries, Nec
Sales $10,000,000-$50,000,000
# of Employees 130
Plant Area (Sq.Ft.) 278,000
Annual Production 7,500,000 Pounds
Production Hrs. Annual 7,488
Location (State) OH
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $358,219 9,551,154 kWh $0.04
Electricity Demand $253,185 28,188 kW-months/year $8.98
Natural Gas $167,022 32,502 MMBtu $5.14
TOTAL ENERGY COSTS $778,426
RECOMMENDED SAVINGS* $85,639 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $56,924
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Water Disposal Personnel Changes Electricity Usage Electricity Demand Natural Gas Water Disposal Personnel Changes
$ kWh $ kW-months/year $ MMBtu $ Tgal $ $
01: 2.3131 RESCHEDULE PLANT OPERATIONS OR REDUCE LOAD TO AVOID PEAKS Savings:
$15,708
Cost:
-
- - $15,708 1,680 - - - - - - -
-
kWh
$15,708
1,680
kW-months/year
-
-
MMBtu
-
-
Tgal
-
-
$
02: 2.2612 USE COOLING TOWER WATER INSTEAD OF REFRIGERATION Savings:
$8,039
Cost:
$10,000
$(-1,361) (-34,913) $(-1,046) (-108) - - $10,446 2,520,760 - - $(-1,361)
(-34,913)
kWh
$(-1,046)
(-108)
kW-months/year
-
-
MMBtu
$10,446
2,520,760
Tgal
-
-
$
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$4,507
Cost:
$3,496
$3,823 52,769 $395 84 - - - - $289 - $3,823
52,769
kWh
$395
84
kW-months/year
-
-
MMBtu
-
-
Tgal
$289
-
$
04: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$3,025
Cost:
-
$3,025 77,584 - - - - - - - - $3,025
77,584
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
Tgal
-
-
$
05: 2.4151 DEVELOP A REPAIR/REPLACE POLICY Savings:
$1,371
Cost:
$3,440
$991 25,412 $380 41 - - - - - - $991
25,412
kWh
$380
41
kW-months/year
-
-
MMBtu
-
-
Tgal
-
-
$
06: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$1,167
Cost:
-
$843 21,624 $324 35 - - - - - - $843
21,624
kWh
$324
35
kW-months/year
-
-
MMBtu
-
-
Tgal
-
-
$
07: 2.4224 UPGRADE CONTROLS ON COMPRESSORS Savings:
$14,934
Cost:
$2,000
$10,670 273,600 $4,264 456 - - - - - - $10,670
273,600
kWh
$4,264
456
kW-months/year
-
-
MMBtu
-
-
Tgal
-
-
$
08: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$701
Cost:
$1,000
$940 24,112 $361 38 - - - - $(-600) - $940
24,112
kWh
$361
38
kW-months/year
-
-
MMBtu
-
-
Tgal
$(-600)
-
$
09: 2.2514 COVER OPEN TANKS Savings:
$6,896
Cost:
-
- - - - $6,896 1,342 - - - - -
-
kWh
-
-
kW-months/year
$6,896
1,342
MMBtu
-
-
Tgal
-
-
$
10: 2.2514 COVER OPEN TANKS Savings:
$6,786
Cost:
-
$6,786 109,457 - - - - - - - - $6,786
109,457
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
Tgal
-
-
$
11: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT Savings:
$6,234
Cost:
$11,000
- - - - $6,234 1,213 - - - - -
-
kWh
-
-
kW-months/year
$6,234
1,213
MMBtu
-
-
Tgal
-
-
$
12: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT Savings:
$5,453
Cost:
$10,000
- - - - $5,453 1,061 - - - - -
-
kWh
-
-
kW-months/year
$5,453
1,061
MMBtu
-
-
Tgal
-
-
$
13: 2.2514 COVER OPEN TANKS Savings:
$4,954
Cost:
-
$4,954 127,015 - - - - - - - - $4,954
127,015
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
Tgal
-
-
$
14: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT Savings:
$4,482
Cost:
$9,000
- - - - $4,482 872 - - - - -
-
kWh
-
-
kW-months/year
$4,482
872
MMBtu
-
-
Tgal
-
-
$
15: 2.2522 ISOLATE HOT OR COLD EQUIPMENT Savings:
$1,382
Cost:
$1,500
- - - - $1,382 269 - - - - -
-
kWh
-
-
kW-months/year
$1,382
269
MMBtu
-
-
Tgal
-
-
$
TOTAL RECOMMENDED Savings:
$85,639
Cost:
$51,436
$30,671 676,660 $20,386 2,226 $24,447 4,757 $10,446 2,520,760 $(-311) - $30,671
676,660
kWh
$20,386
2,226
kW-months/year
$24,447
4,757
MMBtu
$10,446
2,520,760
Tgal
$(-311)
-
$
TOTAL IMPLEMENTED Savings:
$56,924
Cost:
$7,940
$28,209 658,804 $21,037 2,250 $8,278 1,611 - - $(-600) - $28,209
658,804
kWh
$21,037
2,250
kW-months/year
$8,278
1,611
MMBtu
-
-
Tgal
$(-600)
-
$
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ Tgal $ $
Electricity Usage Electricity Demand Natural Gas Water Disposal Personnel Changes Electricity Usage Electricity Demand Natural Gas Water Disposal Personnel Changes