Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Dayton |
---|---|
Assessment Year | 2012 |
Principal Product | Steel and iron casting |
NAICS | 331513 - Steel Foundries (except Investment) |
SIC | 3325 - Steel Foundries, Nec |
Sales | $10,000,000-$50,000,000 |
# of Employees | 130 |
Plant Area (Sq.Ft.) | 278,000 |
Annual Production | 7,500,000 Pounds |
Production Hrs. Annual | 7,488 |
Location (State) | OH |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $358,219 | 9,551,154 | kWh | $0.04 |
Electricity Demand | $253,185 | 28,188 | kW-months/year | $8.98 |
Natural Gas | $167,022 | 32,502 | MMBtu | $5.14 |
TOTAL ENERGY COSTS | $778,426 | |||
RECOMMENDED SAVINGS* | $85,639 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $56,924 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Personnel Changes | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Personnel Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.3131 RESCHEDULE PLANT OPERATIONS OR REDUCE LOAD TO AVOID PEAKS |
Savings: $15,708 Cost: - |
- | - | $15,708 | 1,680 | - | - | - | - | - | - |
- - kWh |
$15,708 1,680 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2612 USE COOLING TOWER WATER INSTEAD OF REFRIGERATION |
Savings: $8,039 Cost: $10,000 |
$(-1,361) | (-34,913) | $(-1,046) | (-108) | - | - | $10,446 | 2,520,760 | - | - |
$(-1,361) (-34,913) kWh |
$(-1,046) (-108) kW-months/year |
- - MMBtu |
$10,446 2,520,760 Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $4,507 Cost: $3,496 |
$3,823 | 52,769 | $395 | 84 | - | - | - | - | $289 | - |
$3,823 52,769 kWh |
$395 84 kW-months/year |
- - MMBtu |
- - Tgal |
$289 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $3,025 Cost: - |
$3,025 | 77,584 | - | - | - | - | - | - | - | - |
$3,025 77,584 kWh |
- - kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4151 DEVELOP A REPAIR/REPLACE POLICY |
Savings: $1,371 Cost: $3,440 |
$991 | 25,412 | $380 | 41 | - | - | - | - | - | - |
$991 25,412 kWh |
$380 41 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $1,167 Cost: - |
$843 | 21,624 | $324 | 35 | - | - | - | - | - | - |
$843 21,624 kWh |
$324 35 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4224 UPGRADE CONTROLS ON COMPRESSORS |
Savings: $14,934 Cost: $2,000 |
$10,670 | 273,600 | $4,264 | 456 | - | - | - | - | - | - |
$10,670 273,600 kWh |
$4,264 456 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $701 Cost: $1,000 |
$940 | 24,112 | $361 | 38 | - | - | - | - | $(-600) | - |
$940 24,112 kWh |
$361 38 kW-months/year |
- - MMBtu |
- - Tgal |
$(-600) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.2514 COVER OPEN TANKS |
Savings: $6,896 Cost: - |
- | - | - | - | $6,896 | 1,342 | - | - | - | - |
- - kWh |
- - kW-months/year |
$6,896 1,342 MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.2514 COVER OPEN TANKS |
Savings: $6,786 Cost: - |
$6,786 | 109,457 | - | - | - | - | - | - | - | - |
$6,786 109,457 kWh |
- - kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT |
Savings: $6,234 Cost: $11,000 |
- | - | - | - | $6,234 | 1,213 | - | - | - | - |
- - kWh |
- - kW-months/year |
$6,234 1,213 MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT |
Savings: $5,453 Cost: $10,000 |
- | - | - | - | $5,453 | 1,061 | - | - | - | - |
- - kWh |
- - kW-months/year |
$5,453 1,061 MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13: 2.2514 COVER OPEN TANKS |
Savings: $4,954 Cost: - |
$4,954 | 127,015 | - | - | - | - | - | - | - | - |
$4,954 127,015 kWh |
- - kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
14: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT |
Savings: $4,482 Cost: $9,000 |
- | - | - | - | $4,482 | 872 | - | - | - | - |
- - kWh |
- - kW-months/year |
$4,482 872 MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
15: 2.2522 ISOLATE HOT OR COLD EQUIPMENT |
Savings: $1,382 Cost: $1,500 |
- | - | - | - | $1,382 | 269 | - | - | - | - |
- - kWh |
- - kW-months/year |
$1,382 269 MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $85,639 Cost: $51,436 |
$30,671 | 676,660 | $20,386 | 2,226 | $24,447 | 4,757 | $10,446 | 2,520,760 | $(-311) | - | $30,671 676,660 kWh |
$20,386 2,226 kW-months/year |
$24,447 4,757 MMBtu |
$10,446 2,520,760 Tgal |
$(-311) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $56,924 Cost: $7,940 |
$28,209 | 658,804 | $21,037 | 2,250 | $8,278 | 1,611 | - | - | $(-600) | - | $28,209 658,804 kWh |
$21,037 2,250 kW-months/year |
$8,278 1,611 MMBtu |
- - Tgal |
$(-600) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Personnel Changes | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Personnel Changes |