Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Florida
Assessment Year 1996
Principal Product Filtration and Purification Devices
NAICS n/a
SIC 3564 - Blowers And Fans
Sales $10,000,000-$50,000,000
# of Employees 100
Plant Area (Sq.Ft.) 160,000
Annual Production 50,000,000 Pieces
Production Hrs. Annual 7,200
Location (State) FL
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $354,606 7,387,163 kWh $0.05
Electricity Demand $144,224 21,504 kW-months/year $6.71
LPG $1,809 251 MMBtu $7.21
TOTAL ENERGY COSTS $500,639
RECOMMENDED SAVINGS* $145,056 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $23,832
#|Description Savings
Cost
Status Electricity Usage Electricity Demand By-product Production Electricity Usage Electricity Demand By-product Production
$ kWh $ kW-months/year $ $
01: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS Savings:
$97,999
Cost:
$5,544
$81,573 1,773,154 $16,426 2,448 - - $81,573
1,773,154
kWh
$16,426
2,448
kW-months/year
-
-
$
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$14,368
Cost:
$16,471
$12,130 263,775 $2,238 334 - - $12,130
263,775
kWh
$2,238
334
kW-months/year
-
-
$
03: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$2,265
Cost:
$3,303
$1,822 38,101 $443 66 - - $1,822
38,101
kWh
$443
66
kW-months/year
-
-
$
04: 2.1211 MOVE BOILER TO MORE EFFICIENT LOCATION Savings:
$10,185
Cost:
-
$10,185 255,862 - - - - $10,185
255,862
kWh
-
-
kW-months/year
-
-
$
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$8,142
Cost:
$600
$8,142 119,871 - - - - $8,142
119,871
kWh
-
-
kW-months/year
-
-
$
06: 2.7229 AIR CONDITION ONLY SPACE NECESSARY Savings:
$8,857
Cost:
$880
- - $8,857 1,320 - - -
-
kWh
$8,857
1,320
kW-months/year
-
-
$
07: 3.5316 CONTRACT A WOOD PALLET RECYCLING COMPANY Savings:
$3,240
Cost:
-
- - - - $3,240 - -
-
kWh
-
-
kW-months/year
$3,240
-
$
TOTAL RECOMMENDED Savings:
$145,056
Cost:
$26,798
$113,852 2,450,763 $27,964 4,168 $3,240 - $113,852
2,450,763
kWh
$27,964
4,168
kW-months/year
$3,240
-
$
TOTAL IMPLEMENTED Savings:
$23,832
Cost:
$3,903
$20,149 413,834 $443 66 $3,240 - $20,149
413,834
kWh
$443
66
kW-months/year
$3,240
-
$
Savings
Cost
$ kWh $ kW-months/year $ $
Electricity Usage Electricity Demand By-product Production Electricity Usage Electricity Demand By-product Production