IAC logo
IAC Assessment: UF0279
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: UF0279
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Florida
Assessment Year 2001
Principal Product Medical Filtering and Separating Membranes
NAICS n/a
SIC 3589 - Service Industry Machinery, Nec
Sales $10,000,000-$50,000,000
# of Employees 130
Plant Area (Sq.Ft.) 600,000
Annual Production 9,200,000 Pieces
Production Hrs. Annual 6,000
Location (State) FL
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $194,847 7,658,400 kWh $0.03
Electricity Demand $139,245 16,248 kW-months/year $8.57
Natural Gas $295,240 34,089 MMBtu $8.66
TOTAL ENERGY COSTS $629,332
RECOMMENDED SAVINGS* $49,175 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $24,711
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Administrative Changes Ancillary Material Cost Primary Product Electricity Usage Electricity Demand Administrative Changes Ancillary Material Cost Primary Product
$ kWh $ kW-months/year $ $ $ $ $ $
01: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$9,057
Cost:
$10,208
$5,560 222,382 $3,497 34 - - - - - - $5,560
222,382
kWh
$3,497
34
kW-months/year
-
-
$
-
-
$
-
-
$
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$696
Cost:
$660
$413 16,500 $283 3 - - - - - - $413
16,500
kWh
$283
3
kW-months/year
-
-
$
-
-
$
-
-
$
03: 2.7491 INSULATE GLAZING, WALLS, CEILINGS, AND ROOFS Savings:
$20,871
Cost:
$62,226
$20,871 474,351 - - - - - - - - $20,871
474,351
kWh
-
-
kW-months/year
-
-
$
-
-
$
-
-
$
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$2,241
Cost:
$1,520
$569 22,776 $267 3 $380 - $1,025 - - - $569
22,776
kWh
$267
3
kW-months/year
$380
-
$
$1,025
-
$
-
-
$
05: 2.7124 MAKE A PRACTICE OF TURNING OFF LIGHTS WHEN NOT NEEDED Savings:
$2,260
Cost:
-
$1,341 53,640 $919 9 - - - - - - $1,341
53,640
kWh
$919
9
kW-months/year
-
-
$
-
-
$
-
-
$
06: 2.7145 INSTALL SKYLIGHTS Savings:
$2,897
Cost:
$3,188
$1,035 41,399 $1,892 18 $(-30) - - - - - $1,035
41,399
kWh
$1,892
18
kW-months/year
$(-30)
-
$
-
-
$
-
-
$
07: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$2,853
Cost:
$767
$2,853 64,848 - - - - - - - - $2,853
64,848
kWh
-
-
kW-months/year
-
-
$
-
-
$
-
-
$
08: 3.5316 CONTRACT A WOOD PALLET RECYCLING COMPANY Savings:
$1,800
Cost:
-
- - - - $1,800 - - - - - -
-
kWh
-
-
kW-months/year
$1,800
-
$
-
-
$
-
-
$
09: 4.448 INSTALL AUTOMATIC PART STORAGE / RETREVAL SYSTEM Savings:
$6,500
Cost:
$4,612
- - - - - - - - $6,500 - -
-
kWh
-
-
kW-months/year
-
-
$
-
-
$
$6,500
-
$
TOTAL RECOMMENDED Savings:
$49,175
Cost:
$83,181
$32,642 895,896 $6,858 67 $2,150 - $1,025 - $6,500 - $32,642
895,896
kWh
$6,858
67
kW-months/year
$2,150
-
$
$1,025
-
$
$6,500
-
$
TOTAL IMPLEMENTED Savings:
$24,711
Cost:
$17,107
$10,323 363,646 $4,683 46 $2,180 - $1,025 - $6,500 - $10,323
363,646
kWh
$4,683
46
kW-months/year
$2,180
-
$
$1,025
-
$
$6,500
-
$
Savings
Cost
$ kWh $ kW-months/year $ $ $ $ $ $
Electricity Usage Electricity Demand Administrative Changes Ancillary Material Cost Primary Product Electricity Usage Electricity Demand Administrative Changes Ancillary Material Cost Primary Product