IAC logo
IAC Assessment: UF0347
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: UF0347
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Florida
Assessment Year 2004
Principal Product Livestock Feed
NAICS 115114 - Postharvest Crop Activities (except Cotton Ginning)
SIC 723 - Beauty Shops
Sales <$500,000
# of Employees 90
Plant Area (Sq.Ft.) 52,500
Annual Production 0 Tons
Production Hrs. Annual 4,680
Location (State) FL
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $162,940 1,973,286 kWh $0.08
Electricity Demand $49,368 7,102 kW-months/year $6.95
Natural Gas $46,902 5,067 MMBtu $9.26
TOTAL ENERGY COSTS $259,210
RECOMMENDED SAVINGS* $34,793 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas
$ kWh $ kW-months/year $ MMBtu
01: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$5,948
Cost:
$9,014
$3,613 65,687 $2,335 28 - - $3,613
65,687
kWh
$2,335
28
kW-months/year
-
-
MMBtu
02: 2.1213 DIRECT WARMEST AIR TO COMBUSTION INTAKE Savings:
$4,683
Cost:
$24,500
- - - - $4,683 5,036 -
-
kWh
-
-
kW-months/year
$4,683
5,036
MMBtu
03: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$9,477
Cost:
$23,746
$6,391 116,192 $3,086 37 - - $6,391
116,192
kWh
$3,086
37
kW-months/year
-
-
MMBtu
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$1,920
Cost:
$1,902
$1,450 30,608 $470 6 - - $1,450
30,608
kWh
$470
6
kW-months/year
-
-
MMBtu
05: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$2,256
Cost:
-
$2,256 27,378 - - - - $2,256
27,378
kWh
-
-
kW-months/year
-
-
MMBtu
06: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$1,861
Cost:
-
$1,861 12,508 - - - - $1,861
12,508
kWh
-
-
kW-months/year
-
-
MMBtu
07: 2.7124 MAKE A PRACTICE OF TURNING OFF LIGHTS WHEN NOT NEEDED Savings:
$4,852
Cost:
$1,004
$4,572 83,123 $280 3 - - $4,572
83,123
kWh
$280
3
kW-months/year
-
-
MMBtu
08: 2.7131 ADD AREA LIGHTING SWITCHES Savings:
$1,051
Cost:
$3,395
$1,051 12,737 - - - - $1,051
12,737
kWh
-
-
kW-months/year
-
-
MMBtu
09: 2.2135 REPAIR AND ELIMINATE STEAM LEAKS Savings:
$2,746
Cost:
$800
- - - - $2,746 2,747 -
-
kWh
-
-
kW-months/year
$2,746
2,747
MMBtu
TOTAL RECOMMENDED Savings:
$34,793
Cost:
$64,361
$21,193 348,233 $6,171 74 $7,429 7,783 $21,193
348,233
kWh
$6,171
74
kW-months/year
$7,429
7,783
MMBtu
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - -
-
kWh
-
-
kW-months/year
-
-
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ MMBtu
Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas