Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Florida
Assessment Year 2004
Principal Product Titanium and Zirconium
NAICS 331491 - Nonferrous Metal (except Copper and Aluminum) Rolling, Drawing, and Extruding
SIC 3356 - Nonferrous Rolling And Drawing, Nec
Sales $10,000,000-$50,000,000
# of Employees 102
Plant Area (Sq.Ft.) 87,120
Annual Production 190,000 Tons
Production Hrs. Annual 8,736
Location (State) FL
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $2,312,412 53,241,209 kWh $0.04
Natural Gas $22,084 18,669 MMBtu $1.18
TOTAL ENERGY COSTS $2,334,496
RECOMMENDED SAVINGS* $292,078 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $25,329
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Solid Waste (non-haz) Electricity Usage Electricity Demand Natural Gas Solid Waste (non-haz)
$ kWh $ kW-months/year $ MMBtu $ lb
01: 2.7124 MAKE A PRACTICE OF TURNING OFF LIGHTS WHEN NOT NEEDED Savings:
$3,410
Cost:
$1,004
$2,782 64,696 $628 26 - - - - $2,782
64,696
kWh
$628
26
kW-months/year
-
-
MMBtu
-
-
lb
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$7,704
Cost:
$5,952
$7,233 168,199 $471 19 - - - - $7,233
168,199
kWh
$471
19
kW-months/year
-
-
MMBtu
-
-
lb
03: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$22,503
Cost:
-
$22,503 523,330 - - - - - - $22,503
523,330
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
lb
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$1,480
Cost:
$3,600
$1,480 - - - - - - - $1,480
-
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
lb
05: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$14,215
Cost:
$35,243
$13,342 310,285 $873 36 - - - - $13,342
310,285
kWh
$873
36
kW-months/year
-
-
MMBtu
-
-
lb
06: 2.1213 DIRECT WARMEST AIR TO COMBUSTION INTAKE Savings:
$16,846
Cost:
$85,000
- - - - $16,846 14,276 - - -
-
kWh
-
-
kW-months/year
$16,846
14,276
MMBtu
-
-
lb
07: 3.5242 RECOVER METALS FROM SPENT SOLUTIONS AND RECYCLE Savings:
$225,920
Cost:
$200,000
- - - - - - $225,920 2,940,000 -
-
kWh
-
-
kW-months/year
-
-
MMBtu
$225,920
2,940,000
lb
TOTAL RECOMMENDED Savings:
$292,078
Cost:
$330,799
$47,340 1,066,510 $1,972 81 $16,846 14,276 $225,920 2,940,000 $47,340
1,066,510
kWh
$1,972
81
kW-months/year
$16,846
14,276
MMBtu
$225,920
2,940,000
lb
TOTAL IMPLEMENTED Savings:
$25,329
Cost:
$42,199
$23,357 543,180 $1,972 81 - - - - $23,357
543,180
kWh
$1,972
81
kW-months/year
-
-
MMBtu
-
-
lb
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ lb
Electricity Usage Electricity Demand Natural Gas Solid Waste (non-haz) Electricity Usage Electricity Demand Natural Gas Solid Waste (non-haz)