Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Florida |
---|---|
Assessment Year | 2017 |
Principal Product | Turpentines and Tall Oils (30 products) |
NAICS | 325194 - Cyclic Crude, Intermediate, and Gum and Wood Chemical Manufacturing |
SIC | 2861 - Gum And Wood Chemicals |
Sales | $50,000,000-$100,000,000 |
# of Employees | 75 |
Plant Area (Sq.Ft.) | 740,520 |
Annual Production | 70,939,000,000 Pounds |
Production Hrs. Annual | 8,736 |
Location (State) | FL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $2,617,971 | 32,723,792 | kWh | $0.08 |
Natural Gas | $3,538,713 | 1,363,444 | MMBtu | $2.60 |
TOTAL ENERGY COSTS | $6,156,684 | |||
RECOMMENDED SAVINGS* | $1,711,448 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $317,468 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Fees | Natural Gas | Electricity Usage | Electricity Fees | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | $ | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.3415 USE A FOSSIL FUEL ENGINE TO COGENERATE ELECTRICITY OR MOTIVE POWER; AND UTILIZE HEAT |
Savings: $1,393,980 Cost: $3,306,000 |
$2,040,000 | 25,500,000 | - | - | $(-646,020) | (-217,515) |
$2,040,000 25,500,000 kWh |
- - $ |
$(-646,020) (-217,515) MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $154,176 Cost: $60,284 |
- | - | $154,176 | - | - | - |
- - kWh |
$154,176 - $ |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $77,438 Cost: $2,184 |
$77,438 | 967,980 | - | - | - | - |
$77,438 967,980 kWh |
- - $ |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2135 REPAIR AND ELIMINATE STEAM LEAKS |
Savings: $32,236 Cost: $1,794 |
- | - | - | - | $32,236 | 10,854 |
- - kWh |
- - $ |
$32,236 10,854 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $29,058 Cost: $39,050 |
$29,058 | 363,228 | - | - | - | - |
$29,058 363,228 kWh |
- - $ |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2611 MODERATE COOLING TOWER OUTLET TEMPERATURE |
Savings: $9,110 Cost: $700 |
$9,110 | 113,880 | - | - | - | - |
$9,110 113,880 kWh |
- - $ |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.2515 USE OPTIMUM THICKNESS INSULATION |
Savings: $6,596 Cost: $11,216 |
- | - | - | - | $6,596 | 2,221 |
- - kWh |
- - $ |
$6,596 2,221 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7121 UTILIZE DAYLIGHT WHENEVER POSSIBLE IN LIEU OF ARTIFICIAL LIGHT |
Savings: $5,834 Cost: - |
$5,834 | 72,927 | - | - | - | - |
$5,834 72,927 kWh |
- - $ |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $3,020 Cost: $482 |
$3,020 | 37,755 | - | - | - | - |
$3,020 37,755 kWh |
- - $ |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $1,711,448 Cost: $3,421,710 |
$2,164,460 | 27,055,770 | $154,176 | - | $(-607,188) | (-204,440) | $2,164,460 27,055,770 kWh |
$154,176 - $ |
$(-607,188) (-204,440) MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $317,468 Cost: $115,710 |
$124,460 | 1,555,770 | $154,176 | - | $38,832 | 13,075 | $124,460 1,555,770 kWh |
$154,176 - $ |
$38,832 13,075 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | $ | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Fees | Natural Gas | Electricity Usage | Electricity Fees | Natural Gas |