Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Florida |
---|---|
Assessment Year | 2017 |
Principal Product | Citrus and fruit flavors |
NAICS | 311930 - Flavoring Syrup and Concentrate Manufacturing |
SIC | 2087 - Flavoring Extracts And Syrups, Nec |
Sales | $50,000,000-$100,000,000 |
# of Employees | 62 |
Plant Area (Sq.Ft.) | 313,632 |
Annual Production | 11,000,000 Pounds |
Production Hrs. Annual | 6,864 |
Location (State) | FL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $285,596 | 4,325,800 | kWh | $0.07 |
Electricity Demand | $83,971 | 9,115 | kW-months/year | $9.21 |
Natural Gas | $71,772 | 29,133 | MMBtu | $2.46 |
TOTAL ENERGY COSTS | $937,332 | |||
RECOMMENDED SAVINGS* | $67,896 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $62,186 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $40,154 Cost: $30,844 |
$31,994 | 484,751 | $8,160 | 886 | - | - |
$31,994 484,751 kWh |
$8,160 886 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7425 CLEAN OR COLOR ROOF TO REDUCE SOLAR LOAD |
Savings: $7,847 Cost: $20,000 |
$7,847 | 118,887 | - | - | - | - |
$7,847 118,887 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7226 USE COMPUTER PROGRAMS TO OPTIMIZE HVAC PERFORMANCE |
Savings: $5,710 Cost: $7,580 |
$5,710 | 86,516 | - | - | - | - |
$5,710 86,516 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2162 REDUCE EXCESS STEAM BLEEDING |
Savings: $4,320 Cost: - |
- | - | - | - | $4,320 | 1,756 |
- - kWh |
- - kW-months/year |
$4,320 1,756 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES |
Savings: $3,740 Cost: $2,882 |
- | - | - | - | $3,740 | 1,520 |
- - kWh |
- - kW-months/year |
$3,740 1,520 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $3,693 Cost: $6,775 |
$2,788 | 42,249 | $905 | 98 | - | - |
$2,788 42,249 kWh |
$905 98 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO |
Savings: $2,432 Cost: - |
- | - | - | - | $2,432 | 989 |
- - kWh |
- - kW-months/year |
$2,432 989 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $67,896 Cost: $68,081 |
$48,339 | 732,403 | $9,065 | 984 | $10,492 | 4,265 | $48,339 732,403 kWh |
$9,065 984 kW-months/year |
$10,492 4,265 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $62,186 Cost: $60,501 |
$42,629 | 645,887 | $9,065 | 984 | $10,492 | 4,265 | $42,629 645,887 kWh |
$9,065 984 kW-months/year |
$10,492 4,265 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas |