Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Florida |
---|---|
Assessment Year | 2023 |
Principal Product | Joint Treatment Compound |
NAICS | 327420 - Gypsum Product Manufacturing |
SIC | 3275 - Gypsum Products |
Sales | $50,000,000-$100,000,000 |
# of Employees | 32 |
Plant Area (Sq.Ft.) | 81,225 |
Annual Production | 18,200 Thousand Gallons |
Production Hrs. Annual | 8,760 |
Location (State) | FL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $161,768 | 2,109,234 | kWh | $0.08 |
Electricity Demand | $64,604 | 24,531 | kW-months/year | $2.63 |
Electricity Fees | $48,315 | - | $ | - |
TOTAL ENERGY COSTS | $274,687 | |||
RECOMMENDED SAVINGS* | $82,982 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $62,152 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Administrative Changes | Electricity Usage | Electricity Demand | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.3191 USE DEMAND CONTROLLER OR LOAD SHEDDER |
Savings: $20,830 Cost: $11,347 |
$16,241 | 210,923 | $4,589 | 1,742 | - | - |
$16,241 210,923 kWh |
$4,589 1,742 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $17,863 Cost: $38,735 |
$14,822 | 192,492 | $3,041 | 1,154 | - | - |
$14,822 192,492 kWh |
$3,041 1,154 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4112 INSTALL SOFT-START TO ELIMINATE NUISANCE TRIPS |
Savings: $4,976 Cost: $11,866 |
$4,976 | 64,622 | - | - | - | - |
$4,976 64,622 kWh |
- - kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $4,508 Cost: $584 |
$4,508 | 58,548 | - | - | - | - |
$4,508 58,548 kWh |
- - kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2623 MINIMIZE CONDENSER COOLING WATER TEMPERATURE |
Savings: $1,132 Cost: $1,440 |
$1,132 | 14,700 | - | - | - | - |
$1,132 14,700 kWh |
- - kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7132 INSTALL TIMERS ON LIGHT SWITCHES IN LITTLE USED AREAS |
Savings: $1,118 Cost: $591 |
$1,118 | 14,515 | - | - | - | - |
$1,118 14,515 kWh |
- - kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 4.424 IMPROVE SPACE COMFORT CONDITIONING |
Savings: $32,555 Cost: $3,179 |
$(-321) | (-4,165) | $(-111) | (-42) | $32,987 | - |
$(-321) (-4,165) kWh |
$(-111) (-42) kW-months/year |
$32,987 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $82,982 Cost: $67,742 |
$42,476 | 551,635 | $7,519 | 2,855 | $32,987 | - | $42,476 551,635 kWh |
$7,519 2,855 kW-months/year |
$32,987 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $62,152 Cost: $56,395 |
$26,235 | 340,712 | $2,930 | 1,112 | $32,987 | - | $26,235 340,712 kWh |
$2,930 1,112 kW-months/year |
$32,987 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Administrative Changes | Electricity Usage | Electricity Demand | Administrative Changes |