Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Kentucky |
---|---|
Assessment Year | 2017 |
Principal Product | Commercial Printing |
NAICS | 323111 - Commercial Printing (except Screen and Books) |
SIC | 2754 - Commercial Printing, Gravure |
Sales | $5,000,000-$10,000,000 |
# of Employees | 135 |
Plant Area (Sq.Ft.) | 40,000 |
Annual Production | 10,000,000 Units |
Production Hrs. Annual | 3,640 |
Location (State) | KY |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $156,353 | 1,878,100 | kWh | $0.08 |
Electricity Demand | $25,149 | 4,420 | kW-months/year | $5.69 |
Electricity Fees | $360 | - | $ | - |
Natural Gas | $23,454 | 3,571 | MMBtu | $6.57 |
TOTAL ENERGY COSTS | $207,562 | |||
RECOMMENDED SAVINGS* | $53,695 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $31,837 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7442 KEEP DOORS AND WINDOWS SHUT WHEN NOT ON USE |
Savings: $7,278 Cost: - |
$6,653 | 80,154 | $625 | 110 | - | - | - | - |
$6,653 80,154 kWh |
$625 110 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $18,467 Cost: $25,474 |
$15,901 | 191,575 | $2,566 | 451 | - | - | - | - |
$15,901 191,575 kWh |
$2,566 451 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $1,276 Cost: $952 |
$1,276 | 15,375 | - | - | - | - | - | - |
$1,276 15,375 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $759 Cost: $60 |
$759 | 9,145 | - | - | - | - | - | - |
$759 9,145 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO |
Savings: $2,260 Cost: $750 |
- | - | - | - | - | - | $2,260 | 344 |
- - kWh |
- - kW-months/year |
- - $ |
$2,260 344 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $8,180 Cost: $18,216 |
- | - | - | - | $8,180 | - | - | - |
- - kWh |
- - kW-months/year |
$8,180 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4152 USE ONLY CERTIFIED MOTOR REPAIR SHOPS |
Savings: $1,143 Cost: $3,928 |
$933 | 11,240 | $210 | 37 | - | - | - | - |
$933 11,240 kWh |
$210 37 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $7,080 Cost: - |
$6,949 | 83,720 | $131 | 23 | - | - | - | - |
$6,949 83,720 kWh |
$131 23 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES |
Savings: $314 Cost: $311 |
$314 | 3,781 | - | - | - | - | - | - |
$314 3,781 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.4224 UPGRADE CONTROLS ON COMPRESSORS |
Savings: $2,600 Cost: $5,000 |
$2,156 | 25,975 | $444 | 78 | - | - | - | - |
$2,156 25,975 kWh |
$444 78 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $4,338 Cost: $5,754 |
$2,250 | 27,115 | $467 | 82 | - | - | $1,621 | 247 |
$2,250 27,115 kWh |
$467 82 kW-months/year |
- - $ |
$1,621 247 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $53,695 Cost: $60,445 |
$37,191 | 448,080 | $4,443 | 781 | $8,180 | - | $3,881 | 591 | $37,191 448,080 kWh |
$4,443 781 kW-months/year |
$8,180 - $ |
$3,881 591 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $31,837 Cost: $35,725 |
$27,992 | 337,245 | $3,845 | 676 | - | - | - | - | $27,992 337,245 kWh |
$3,845 676 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas |