IAC logo
IAC Assessment: UU0043
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: UU0043
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Utah
Assessment Year 2003
Principal Product salt
NAICS 325998 - All Other Miscellaneous Chemical Product and Preparation Manufacturing
SIC 2899 - Chemical Preparations, Nec
Sales n/a
# of Employees 141
Plant Area (Sq.Ft.) 75,000
Annual Production 600,000 Tons
Production Hrs. Annual 8,760
Location (State) UT
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $346,458 12,490,820 kWh $0.03
Electricity Demand $191,395 278,436 kW-months/year $0.69
Natural Gas $202,461 168,129 MMBtu $1.20
TOTAL ENERGY COSTS $740,314
RECOMMENDED SAVINGS* $32,568 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $16,395
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Electricity Usage Electricity Demand
$ kWh $ kW-months/year
01: 2.3212 OPTIMIZE PLANT POWER FACTOR Savings:
$3,833
Cost:
$5,820
- - $3,833 419 -
-
kWh
$3,833
419
kW-months/year
02: 2.3131 RESCHEDULE PLANT OPERATIONS OR REDUCE LOAD TO AVOID PEAKS Savings:
$5,032
Cost:
-
- - $5,032 600 -
-
kWh
$5,032
600
kW-months/year
03: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$13,718
Cost:
$32,302
$9,484 330,277 $4,234 504 $9,484
330,277
kWh
$4,234
504
kW-months/year
04: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$1,467
Cost:
$1,500
$1,048 36,510 $419 50 $1,048
36,510
kWh
$419
50
kW-months/year
05: 2.4314 USE SYNTHETIC LUBRICANT Savings:
$4,235
Cost:
$400
$3,280 114,231 $955 114 $3,280
114,231
kWh
$955
114
kW-months/year
06: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE Savings:
$790
Cost:
$400
$188 6,548 $602 72 $188
6,548
kWh
$602
72
kW-months/year
07: 2.7121 UTILIZE DAYLIGHT WHENEVER POSSIBLE IN LIEU OF ARTIFICIAL LIGHT Savings:
$2,677
Cost:
-
$1,711 59,568 $966 115 $1,711
59,568
kWh
$966
115
kW-months/year
08: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$816
Cost:
$406
$583 20,287 $233 28 $583
20,287
kWh
$233
28
kW-months/year
TOTAL RECOMMENDED Savings:
$32,568
Cost:
$40,828
$16,294 567,421 $16,274 1,902 $16,294
567,421
kWh
$16,274
1,902
kW-months/year
TOTAL IMPLEMENTED Savings:
$16,395
Cost:
$32,302
$11,195 389,845 $5,200 619 $11,195
389,845
kWh
$5,200
619
kW-months/year
Savings
Cost
$ kWh $ kW-months/year
Electricity Usage Electricity Demand Electricity Usage Electricity Demand