Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Utah |
---|---|
Assessment Year | 2017 |
Principal Product | NA |
NAICS | 712130 - Zoos and Botanical Gardens |
SIC | 7999 - Amusement And Recreation, Nec |
Sales | $10,000,000-$50,000,000 |
# of Employees | 100 |
Plant Area (Sq.Ft.) | 1,873,000 |
Annual Production | 1,000,000 Units |
Production Hrs. Annual | 3,150 |
Location (State) | UT |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $141,778 | 3,341,177 | kWh | $0.04 |
Electricity Demand | $97,338 | 9,007 | kW-months/year | $10.81 |
Electricity Fees | $137,517 | - | $ | - |
Natural Gas | $119,929 | 40,406 | MMBtu | $2.97 |
TOTAL ENERGY COSTS | $496,562 | |||
RECOMMENDED SAVINGS* | $30,703 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $20,848 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.3131 RESCHEDULE PLANT OPERATIONS OR REDUCE LOAD TO AVOID PEAKS |
Savings: $12,503 Cost: - |
- | - | $9,796 | 670 | $2,707 | - | - | - |
- - kWh |
$9,796 670 kW-months/year |
$2,707 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $5,444 Cost: $5,000 |
- | - | - | - | $5,444 | - | - | - |
- - kWh |
- - kW-months/year |
$5,444 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.1311 REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT |
Savings: $4,630 Cost: $3,140 |
$1,920 | 45,386 | $2,537 | 206 | $832 | - | $(-660) | (-155) |
$1,920 45,386 kWh |
$2,537 206 kW-months/year |
$832 - $ |
$(-660) (-155) MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7423 REDUCE HEAT GAIN BY WINDOW TINTING |
Savings: $3,392 Cost: $10,800 |
$2,329 | 55,066 | $801 | 65 | $263 | - | - | - |
$2,329 55,066 kWh |
$801 65 kW-months/year |
$263 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2622 REPLACE EXISTING CHILLER WITH HIGH EFFICIENCY MODEL |
Savings: $1,833 Cost: $4,266 |
$1,335 | 31,554 | $375 | 30 | $123 | - | - | - |
$1,335 31,554 kWh |
$375 30 kW-months/year |
$123 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $980 Cost: - |
- | - | - | - | - | - | $980 | 230 |
- - kWh |
- - kW-months/year |
- - $ |
$980 230 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS |
Savings: $854 Cost: $1,702 |
$178 | 4,217 | $200 | 16 | $65 | - | $410 | 96 |
$178 4,217 kWh |
$200 16 kW-months/year |
$65 - $ |
$410 96 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $681 Cost: $1,463 |
$263 | 6,214 | $315 | 26 | $103 | - | - | - |
$263 6,214 kWh |
$315 26 kW-months/year |
$103 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7224 REDUCE SPACE CONDITIONING DURING NON-WORKING HOURS |
Savings: $386 Cost: - |
$333 | 7,868 | - | - | - | - | $53 | 12 |
$333 7,868 kWh |
- - kW-months/year |
- - $ |
$53 12 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $30,703 Cost: $26,371 |
$6,358 | 150,305 | $14,023 | 1,013 | $9,538 | - | $784 | 184 | $6,358 150,305 kWh |
$14,023 1,013 kW-months/year |
$9,538 - $ |
$784 184 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $20,848 Cost: $8,165 |
$774 | 18,299 | $10,310 | 712 | $8,320 | - | $1,444 | 339 | $774 18,299 kWh |
$10,310 712 kW-months/year |
$8,320 - $ |
$1,444 339 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas |