Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Utah |
---|---|
Assessment Year | 2019 |
Principal Product | Propellant Pellets |
NAICS | 336390 - Other Motor Vehicle Parts Manufacturing |
SIC | 3714 - Motor Vehicle Parts And Accessories |
Sales | $5,000,000-$10,000,000 |
# of Employees | 350 |
Plant Area (Sq.Ft.) | 188,625 |
Annual Production | 3,500 Units |
Production Hrs. Annual | 8,760 |
Location (State) | UT |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $997,805 | 30,555,960 | kWh | $0.03 |
Electricity Demand | $711,435 | 53,836 | kW-months/year | $13.21 |
Natural Gas | $354,362 | 146,505 | MMBtu | $2.42 |
TOTAL ENERGY COSTS | $2,063,602 | |||
RECOMMENDED SAVINGS* | $1,033,816 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $199,264 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.3415 USE A FOSSIL FUEL ENGINE TO COGENERATE ELECTRICITY OR MOTIVE POWER; AND UTILIZE HEAT |
Savings: $567,696 Cost: $2,355,000 |
$596,044 | 18,250,000 | $330,323 | 25,006 | $(-241,671) | (-99,864) | $(-117,000) | - |
$596,044 18,250,000 kWh |
$330,323 25,006 kW-months/year |
$(-241,671) (-99,864) MMBtu |
$(-117,000) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.3417 USE WASTE HEAT WITH A CLOSED-CYCLE GAS TURBINE-GENERATOR SET TO COGENERATE ELECTRICITY AND HEAT |
Savings: $262,908 Cost: $2,299,950 |
$342,560 | 10,380,600 | $187,846 | 14,220 | $(-174,073) | (-71,950) | $(-93,425) | - |
$342,560 10,380,600 kWh |
$187,846 14,220 kW-months/year |
$(-174,073) (-71,950) MMBtu |
$(-93,425) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $170,761 Cost: $461,313 |
$110,730 | 3,390,380 | $60,031 | 4,544 | - | - | - | - |
$110,730 3,390,380 kWh |
$60,031 4,544 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $18,288 Cost: $2,040 |
$11,773 | 360,314 | $6,515 | 493 | - | - | - | - |
$11,773 360,314 kWh |
$6,515 493 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $10,215 Cost: $3,044 |
- | - | - | - | $10,215 | 4,221 | - | - |
- - kWh |
- - kW-months/year |
$10,215 4,221 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.3132 RECHARGE BATTERIES ON DURING OFF-PEAK DEMAND PERIODS |
Savings: $3,947 Cost: $2,000 |
- | - | $3,947 | 299 | - | - | - | - |
- - kWh |
$3,947 299 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $1,033,816 Cost: $5,123,347 |
$1,061,107 | 32,381,294 | $588,662 | 44,562 | $(-405,529) | (-167,593) | $(-210,425) | - | $1,061,107 32,381,294 kWh |
$588,662 44,562 kW-months/year |
$(-405,529) (-167,593) MMBtu |
$(-210,425) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $199,264 Cost: $466,397 |
$122,503 | 3,750,694 | $66,546 | 5,038 | $10,215 | 4,221 | - | - | $122,503 3,750,694 kWh |
$66,546 5,038 kW-months/year |
$10,215 4,221 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Ancillary Material Cost |