Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Utah
Assessment Year 2020
Principal Product Water
NAICS 221310 - Water Supply and Irrigation Systems
SIC 4941 - Water Supply
Sales $5,000,000-$10,000,000
# of Employees 10
Plant Area (Sq.Ft.) 2,500
Annual Production 7,500 Thousand Gallons
Production Hrs. Annual 2,921
Location (State) UT
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $94,055 1,858,800 kWh $0.05
Electricity Demand $55,580 6,108 kW-months/year $9.10
Electricity Fees $3,600 - $ -
TOTAL ENERGY COSTS $153,235
RECOMMENDED SAVINGS* $16,349 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $13,128
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Electricity Usage Electricity Demand
$ kWh $ kW-months/year
01: 2.3131 RESCHEDULE PLANT OPERATIONS OR REDUCE LOAD TO AVOID PEAKS Savings:
$5,906
Cost:
-
- - $5,906 649 -
-
kWh
$5,906
649
kW-months/year
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$3,729
Cost:
$15,550
$2,235 44,190 $1,494 164 $2,235
44,190
kWh
$1,494
164
kW-months/year
03: 2.3131 RESCHEDULE PLANT OPERATIONS OR REDUCE LOAD TO AVOID PEAKS Savings:
$3,221
Cost:
$8,000
- - $3,221 354 -
-
kWh
$3,221
354
kW-months/year
04: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA Savings:
$3,063
Cost:
-
$2,346 46,371 $717 79 $2,346
46,371
kWh
$717
79
kW-months/year
05: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$251
Cost:
-
$186 3,674 $65 7 $186
3,674
kWh
$65
7
kW-months/year
06: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$178
Cost:
-
$134 2,651 $44 5 $134
2,651
kWh
$44
5
kW-months/year
TOTAL RECOMMENDED Savings:
$16,349
Cost:
$23,550
$4,901 96,886 $11,448 1,258 $4,901
96,886
kWh
$11,448
1,258
kW-months/year
TOTAL IMPLEMENTED Savings:
$13,128
Cost:
$15,550
$4,901 96,886 $8,227 904 $4,901
96,886
kWh
$8,227
904
kW-months/year
Savings
Cost
$ kWh $ kW-months/year
Electricity Usage Electricity Demand Electricity Usage Electricity Demand