Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Washington |
---|---|
Assessment Year | 2007 |
Principal Product | Aluminum cans |
NAICS | 332431 - Metal Can Manufacturing |
SIC | 3411 - Metal Cans |
Sales | $50,000,000-$100,000,000 |
# of Employees | 109 |
Plant Area (Sq.Ft.) | 180,000 |
Annual Production | 1,800,000,000 Pieces |
Production Hrs. Annual | 8,640 |
Location (State) | WA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $1,127,837 | 21,663,600 | kWh | $0.05 |
Electricity Demand | $211,746 | 36,048 | kW-months/year | $5.87 |
Electricity Fees | $11,416 | - | $ | - |
Natural Gas | $866,333 | 78,076 | MMBtu | $11.10 |
TOTAL ENERGY COSTS | $2,333,908 | |||
RECOMMENDED SAVINGS* | $176,769 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $11,402 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Personnel Changes | Water Consumption | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Personnel Changes | Water Consumption | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | $ | $ | $ | Tgal | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4226 USE / PURCHASE OPTIMUM SIZED COMPRESSOR |
Savings: $93,799 Cost: $136,650 |
$81,034 | 1,460,071 | $12,765 | 2,086 | - | - | - | - | - | - | - | - |
$81,034 1,460,071 kWh |
$12,765 2,086 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $27,889 Cost: $1,720 |
$28,640 | 516,031 | $4,449 | 727 | - | - | - | - | $(-5,200) | - | - | - |
$28,640 516,031 kWh |
$4,449 727 kW-months/year |
- - MMBtu |
- - Tgal |
$(-5,200) - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $28,369 Cost: $138,420 |
$24,556 | 442,443 | $3,813 | 623 | - | - | - | - | - | - | - | - |
$24,556 442,443 kWh |
$3,813 623 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $8,031 Cost: $7,140 |
$3,689 | 66,469 | $557 | 91 | - | - | $1,501 | 234,391 | - | - | $2,284 | - |
$3,689 66,469 kWh |
$557 91 kW-months/year |
- - MMBtu |
$1,501 234,391 Tgal |
- - $ |
$2,284 - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.1117 RELOCATE OVEN / FURNACE TO MORE EFFICIENT LOCATION |
Savings: $11,196 Cost: $2,080 |
$9,672 | 174,266 | $1,524 | 249 | - | - | - | - | - | - | - | - |
$9,672 174,266 kWh |
$1,524 249 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.1116 IMPROVE COMBUSTION CONTROL CAPABILITY |
Savings: $4,114 Cost: $3,000 |
- | - | - | - | $5,314 | 454 | - | - | $(-1,200) | - | - | - |
- - kWh |
- - kW-months/year |
$5,314 454 MMBtu |
- - Tgal |
$(-1,200) - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4151 DEVELOP A REPAIR/REPLACE POLICY |
Savings: $3,371 Cost: $1,984 |
$2,960 | 53,327 | $411 | 67 | - | - | - | - | - | - | - | - |
$2,960 53,327 kWh |
$411 67 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $176,769 Cost: $290,994 |
$150,551 | 2,712,607 | $23,519 | 3,843 | $5,314 | 454 | $1,501 | 234,391 | $(-6,400) | - | $2,284 | - | $150,551 2,712,607 kWh |
$23,519 3,843 kW-months/year |
$5,314 454 MMBtu |
$1,501 234,391 Tgal |
$(-6,400) - $ |
$2,284 - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $11,402 Cost: $9,124 |
$6,649 | 119,796 | $968 | 158 | - | - | $1,501 | 234,391 | - | - | $2,284 | - | $6,649 119,796 kWh |
$968 158 kW-months/year |
- - MMBtu |
$1,501 234,391 Tgal |
- - $ |
$2,284 - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | $ | $ | $ | Tgal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Personnel Changes | Water Consumption | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Personnel Changes | Water Consumption |