Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Wisconsin, Milwaukee |
---|---|
Assessment Year | 2002 |
Principal Product | Envelopes |
NAICS | n/a |
SIC | 2677 - Envelopes |
Sales | $1,000,000-$5,000,000 |
# of Employees | 160 |
Plant Area (Sq.Ft.) | 300,000 |
Annual Production | 7,200,000 Pieces |
Production Hrs. Annual | 6,000 |
Location (State) | WI |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $185,704 | 5,802,264 | kWh | $0.03 |
Electricity Demand | $132,713 | 13,738 | kW-months/year | $9.66 |
Electricity Fees | $24,565 | - | $ | - |
Natural Gas | $70,353 | 8,426 | MMBtu | $8.35 |
TOTAL ENERGY COSTS | $413,335 | |||
RECOMMENDED SAVINGS* | $54,886 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $49,805 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $15,331 Cost: $2,200 |
- | - | - | - | $15,331 | 1,836 | - | - |
- - kWh |
- - kW-months/year |
$15,331 1,836 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $9,921 Cost: $15,527 |
$6,505 | 203,280 | $3,416 | 305 | - | - | - | - |
$6,505 203,280 kWh |
$3,416 305 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $6,222 Cost: $9,800 |
$3,187 | 99,582 | $3,035 | 283 | - | - | - | - |
$3,187 99,582 kWh |
$3,035 283 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7144 INSTALL SPECTRAL REFLECTORS / DELAMP |
Savings: $5,203 Cost: - |
$3,599 | 112,460 | $1,604 | 140 | - | - | - | - |
$3,599 112,460 kWh |
$1,604 140 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $6,879 Cost: $1,996 |
$4,655 | 145,470 | $2,224 | 196 | - | - | - | - |
$4,655 145,470 kWh |
$2,224 196 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7243 IMPROVE AIR CIRCULATION WITH DESTRATIFICATION FANS / OTHER METHODS |
Savings: $4,308 Cost: $8,000 |
$(-517) | (-15,400) | - | - | $4,825 | 578 | - | - |
$(-517) (-15,400) kWh |
- - kW-months/year |
$4,825 578 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 3.7137 REPLACE CLOTH RAGS WITH PAPER TOWELS |
Savings: $3,427 Cost: - |
- | - | - | - | - | - | $3,427 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$3,427 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $1,941 Cost: $740 |
$1,273 | 39,787 | $668 | 60 | - | - | - | - |
$1,273 39,787 kWh |
$668 60 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $1,654 Cost: $6,100 |
$1,654 | 49,236 | - | - | - | - | - | - |
$1,654 49,236 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $54,886 Cost: $44,363 |
$20,356 | 634,415 | $10,947 | 984 | $20,156 | 2,414 | $3,427 | - | $20,356 634,415 kWh |
$10,947 984 kW-months/year |
$20,156 2,414 MMBtu |
$3,427 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $49,805 Cost: $38,263 |
$18,702 | 585,179 | $10,947 | 984 | $20,156 | 2,414 | - | - | $18,702 585,179 kWh |
$10,947 984 kW-months/year |
$20,156 2,414 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes |