Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Wisconsin, Milwaukee |
---|---|
Assessment Year | 2015 |
Principal Product | Transmissions |
NAICS | 333613 - Mechanical Power Transmission Equipment Manufacturing |
SIC | 3568 - Power Transmission Equipment, Nec |
Sales | $100,000,000-$500,000,000 |
# of Employees | 250 |
Plant Area (Sq.Ft.) | 300,000 |
Annual Production | 30,000 Pieces |
Production Hrs. Annual | 6,120 |
Location (State) | WI |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $600,603 | 9,691,916 | kWh | $0.06 |
Electricity Demand | $359,538 | 26,595 | kW-months/year | $13.52 |
Natural Gas | $388,395 | 47,537 | MMBtu | $8.17 |
TOTAL ENERGY COSTS | $1,439,583 | |||
RECOMMENDED SAVINGS* | $178,744 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $51,767 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | One-time Revenue or Avoided Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 3.4145 USE MAGNETIC TECHNOLOGY TO TREAT WATER |
Savings: $7,657 Cost: $15,000 |
- | - | - | - | - | - | $7,657 | 937 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$7,657 937 MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2449 RECOVER HEAT FROM EXHAUSTED STEAM, HOT AIR OR HOT WATER |
Savings: $44,425 Cost: $42,690 |
- | - | - | - | - | - | $44,425 | 5,438 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$44,425 5,438 MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.8112 COMBINE UTILITY METERS |
Savings: $35,185 Cost: $4,450 |
- | - | - | - | $35,185 | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$35,185 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $25,416 Cost: - |
- | - | - | - | - | - | $25,416 | 3,111 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$25,416 3,111 MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS |
Savings: $12,203 Cost: $7,680 |
- | - | - | - | - | - | $12,203 | 1,520 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$12,203 1,520 MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $7,737 Cost: $654 |
- | - | - | - | - | - | $7,737 | 947 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$7,737 947 MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $9,191 Cost: $1,600 |
- | - | - | - | - | - | $9,191 | 1,125 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$9,191 1,125 MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $8,586 Cost: $1,680 |
$6,015 | 97,010 | $2,571 | 190 | - | - | - | - | - | - |
$6,015 97,010 kWh |
$2,571 190 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $4,111 Cost: $1,245 |
$2,883 | 46,500 | $1,228 | 91 | - | - | - | - | - | - |
$2,883 46,500 kWh |
$1,228 91 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $7,592 Cost: $640 |
$5,626 | 90,740 | $1,966 | 145 | - | - | - | - | - | - |
$5,626 90,740 kWh |
$1,966 145 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $6,495 Cost: $10,871 |
$3,519 | 56,757 | - | - | - | - | - | - | $2,976 | - |
$3,519 56,757 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
$2,976 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 3.5316 CONTRACT A WOOD PALLET RECYCLING COMPANY |
Savings: $5,737 Cost: - |
- | - | - | - | - | - | - | - | $5,737 | - |
- - kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
$5,737 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13: 2.3132 RECHARGE BATTERIES ON DURING OFF-PEAK DEMAND PERIODS |
Savings: $3,678 Cost: - |
- | - | - | - | $3,678 | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$3,678 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
14: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $731 Cost: $1,876 |
$518 | 8,356 | $213 | 16 | - | - | - | - | - | - |
$518 8,356 kWh |
$213 16 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $178,744 Cost: $88,386 |
$18,561 | 299,363 | $5,978 | 442 | $38,863 | - | $106,629 | 13,078 | $8,713 | - | $18,561 299,363 kWh |
$5,978 442 kW-months/year |
$38,863 - $ |
$106,629 13,078 MMBtu |
$8,713 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $51,767 Cost: $13,191 |
$15,160 | 244,507 | $4,537 | 335 | $3,678 | - | $25,416 | 3,111 | $2,976 | - | $15,160 244,507 kWh |
$4,537 335 kW-months/year |
$3,678 - $ |
$25,416 3,111 MMBtu |
$2,976 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | One-time Revenue or Avoided Cost |