Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Wisconsin, Milwaukee |
---|---|
Assessment Year | 2018 |
Principal Product | Waste Water Treatment |
NAICS | 221320 - Sewage Treatment Facilities |
SIC | 4952 - Sewerage Systems |
Sales | <$500,000 |
# of Employees | 95 |
Plant Area (Sq.Ft.) | 2,257,403 |
Annual Production | 11,680,000 Thousand Gallons |
Production Hrs. Annual | 8,760 |
Location (State) | WI |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $1,498,531 | 34,438,545 | kWh | $0.04 |
Electricity Demand | $558,896 | 53,509 | kW-months/year | $10.44 |
Electricity Fees | $250,906 | - | $ | - |
Natural Gas | $881,221 | 213,082 | MMBtu | $4.14 |
TOTAL ENERGY COSTS | $3,189,554 | |||
RECOMMENDED SAVINGS* | $137,310 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $54,971 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Ancillary Material Cost | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4226 USE / PURCHASE OPTIMUM SIZED COMPRESSOR |
Savings: $60,763 Cost: $200,000 |
$45,726 | 1,050,925 | $15,037 | 1,440 | - | - | - | - | - | - |
$45,726 1,050,925 kWh |
$15,037 1,440 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4314 USE SYNTHETIC LUBRICANT |
Savings: $28,087 Cost: $20,000 |
$21,136 | 485,780 | $6,951 | 666 | - | - | - | - | - | - |
$21,136 485,780 kWh |
$6,951 666 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY |
Savings: $11,320 Cost: $99,200 |
$11,320 | 260,185 | - | - | - | - | - | - | - | - |
$11,320 260,185 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $10,991 Cost: $13,400 |
$8,271 | 190,092 | $2,720 | 260 | - | - | - | - | - | - |
$8,271 190,092 kWh |
$2,720 260 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $9,439 Cost: - |
- | - | - | - | - | - | $9,439 | 2,302 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$9,439 2,302 MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $8,920 Cost: $7,291 |
$6,580 | 151,239 | $2,340 | 224 | - | - | - | - | - | - |
$6,580 151,239 kWh |
$2,340 224 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $2,638 Cost: $1,400 |
$1,990 | 45,745 | $648 | 62 | - | - | - | - | - | - |
$1,990 45,745 kWh |
$648 62 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $2,196 Cost: $2,270 |
$1,057 | 24,283 | $348 | 33 | - | - | - | - | $791 | - |
$1,057 24,283 kWh |
$348 33 kW-months/year |
- - $ |
- - MMBtu |
$791 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $1,932 Cost: $1,308 |
$1,305 | 30,000 | $627 | 60 | - | - | - | - | - | - |
$1,305 30,000 kWh |
$627 60 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7144 INSTALL SPECTRAL REFLECTORS / DELAMP |
Savings: $358 Cost: - |
$182 | 4,200 | $176 | 17 | - | - | - | - | - | - |
$182 4,200 kWh |
$176 17 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $350 Cost: - |
$267 | 6,132 | $83 | 8 | - | - | - | - | - | - |
$267 6,132 kWh |
$83 8 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.3132 RECHARGE BATTERIES ON DURING OFF-PEAK DEMAND PERIODS |
Savings: $207 Cost: - |
- | - | - | - | $207 | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$207 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $109 Cost: $98 |
$109 | 2,497 | - | - | - | - | - | - | - | - |
$109 2,497 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $137,310 Cost: $344,967 |
$97,943 | 2,251,078 | $28,930 | 2,770 | $207 | - | $9,439 | 2,302 | $791 | - | $97,943 2,251,078 kWh |
$28,930 2,770 kW-months/year |
$207 - $ |
$9,439 2,302 MMBtu |
$791 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $54,971 Cost: $45,669 |
$40,339 | 927,139 | $13,634 | 1,305 | $207 | - | - | - | $791 | - | $40,339 927,139 kWh |
$13,634 1,305 kW-months/year |
$207 - $ |
- - MMBtu |
$791 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Ancillary Material Cost | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Ancillary Material Cost |