IAC logo
IAC Assessment: WV0073
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: WV0073
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center West Virginia University
Assessment Year 1995
Principal Product Appliance Controls
NAICS n/a
SIC 3363 - Aluminum Die-castings
Sales $10,000,000-$50,000,000
# of Employees 350
Plant Area (Sq.Ft.) 375,000
Annual Production 1,047,340 Pounds
Production Hrs. Annual 6,000
Location (State) PA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $534,698 13,500,879 kWh $0.04
Natural Gas $256,535 62,917 MMBtu $4.08
TOTAL ENERGY COSTS $791,233
RECOMMENDED SAVINGS* $45,367 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $35,066
#|Description Savings
Cost
Status Electricity Usage Natural Gas Electricity Usage Natural Gas
$ kWh $ MMBtu
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$1,063
Cost:
$1,113
$1,063 31,067 - - $1,063
31,067
kWh
-
-
MMBtu
02: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$5,102
Cost:
$11,650
$5,102 149,179 - - $5,102
149,179
kWh
-
-
MMBtu
03: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$1,344
Cost:
$2,220
$1,344 39,273 - - $1,344
39,273
kWh
-
-
MMBtu
04: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$3,159
Cost:
$1,800
$3,159 92,321 - - $3,159
92,321
kWh
-
-
MMBtu
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$952
Cost:
$200
$952 27,843 - - $952
27,843
kWh
-
-
MMBtu
06: 2.1213 DIRECT WARMEST AIR TO COMBUSTION INTAKE Savings:
$5,798
Cost:
$3,300
- - $5,798 1,421 -
-
kWh
$5,798
1,421
MMBtu
07: 2.2511 INSULATE BARE EQUIPMENT Savings:
$11,972
Cost:
$1,278
$11,972 349,648 - - $11,972
349,648
kWh
-
-
MMBtu
08: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO Savings:
$15,977
Cost:
$5,000
- - $15,977 3,916 -
-
kWh
$15,977
3,916
MMBtu
TOTAL RECOMMENDED Savings:
$45,367
Cost:
$26,561
$23,592 689,331 $21,775 5,337 $23,592
689,331
kWh
$21,775
5,337
MMBtu
TOTAL IMPLEMENTED Savings:
$35,066
Cost:
$19,241
$19,089 557,737 $15,977 3,916 $19,089
557,737
kWh
$15,977
3,916
MMBtu
Savings
Cost
$ kWh $ MMBtu
Electricity Usage Natural Gas Electricity Usage Natural Gas