IAC logo
IAC Assessment: WV0093
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: WV0093
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center West Virginia University
Assessment Year 1996
Principal Product Paper products and placemats
NAICS n/a
SIC 2759 - Commercial Printing, Nec
Sales $5,000,000-$10,000,000
# of Employees 86
Plant Area (Sq.Ft.) 147,600
Annual Production 8,500,000 Pieces
Production Hrs. Annual 3,945
Location (State) WV
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $65,744 2,238,277 kWh $0.03
Electricity Demand $76,624 8,362 kW-months/year $9.16
Electricity Fees $1,055 - $ -
Natural Gas $36,583 4,856 MMBtu $7.53
TOTAL ENERGY COSTS $180,006
RECOMMENDED SAVINGS* $6,604 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $2,610
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Administrative Changes Ancillary Material Cost Electricity Usage Electricity Demand Natural Gas Administrative Changes Ancillary Material Cost
$ kWh $ kW-months/year $ MMBtu $ $ $ $
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$581
Cost:
$567
$116 3,810 $465 48 - - - - - - $116
3,810
kWh
$465
48
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
02: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$426
Cost:
$906
$72 2,638 $354 37 - - - - - - $72
2,638
kWh
$354
37
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
03: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$309
Cost:
$160
$309 10,844 - - - - - - - - $309
10,844
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
04: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS Savings:
$967
Cost:
$330
$499 16,999 $468 49 - - - - - - $499
16,999
kWh
$468
49
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
05: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$275
Cost:
$365
$275 9,379 - - - - - - - - $275
9,379
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
06: 2.4314 USE SYNTHETIC LUBRICANT Savings:
$327
Cost:
$630
$327 11,137 - - - - - - - - $327
11,137
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
07: 2.2511 INSULATE BARE EQUIPMENT Savings:
$65
Cost:
$26
$65 2,052 - - - - - - - - $65
2,052
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
08: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT Savings:
$1,190
Cost:
$361
- - - - $1,190 158 - - - - -
-
kWh
-
-
kW-months/year
$1,190
158
MMBtu
-
-
$
-
-
$
09: 3.6193 INSTALL EQUIPMENT (eg COMPACTOR) TO REDUCE DISPOSAL COSTS Savings:
$2,464
Cost:
$7,000
- - - - - - $(-1,286) - $3,750 - -
-
kWh
-
-
kW-months/year
-
-
MMBtu
$(-1,286)
-
$
$3,750
-
$
TOTAL RECOMMENDED Savings:
$6,604
Cost:
$10,345
$1,663 56,859 $1,287 134 $1,190 158 $(-1,286) - $3,750 - $1,663
56,859
kWh
$1,287
134
kW-months/year
$1,190
158
MMBtu
$(-1,286)
-
$
$3,750
-
$
TOTAL IMPLEMENTED Savings:
$2,610
Cost:
$2,593
$1,323 45,428 $1,287 134 - - - - - - $1,323
45,428
kWh
$1,287
134
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ $ $ $
Electricity Usage Electricity Demand Natural Gas Administrative Changes Ancillary Material Cost Electricity Usage Electricity Demand Natural Gas Administrative Changes Ancillary Material Cost