Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | West Virginia University |
---|---|
Assessment Year | 1996 |
Principal Product | Coatings for Packages and Cans |
NAICS | n/a |
SIC | 2851 - Paints And Allied Products |
Sales | $10,000,000-$50,000,000 |
# of Employees | 50 |
Plant Area (Sq.Ft.) | 84,000 |
Annual Production | 1,000 Thousand Gallons |
Production Hrs. Annual | 3,500 |
Location (State) | PA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $37,308 | 987,104 | kWh | $0.04 |
Electricity Demand | $21,353 | 4,150 | kW-months/year | $5.15 |
Electricity Fees | $3,676 | - | $ | - |
Natural Gas | $42,216 | 10,373 | MMBtu | $4.07 |
TOTAL ENERGY COSTS | $104,553 | |||
RECOMMENDED SAVINGS* | $23,595 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $9,124 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $2,071 Cost: $261 |
$835 | 19,637 | $1,236 | 235 | - | - | - | - |
$835 19,637 kWh |
$1,236 235 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $256 Cost: $573 |
$77 | 1,758 | $179 | 31 | - | - | - | - |
$77 1,758 kWh |
$179 31 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $207 Cost: $30 |
$207 | 4,982 | - | - | - | - | - | - |
$207 4,982 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7241 INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT |
Savings: $753 Cost: $4,725 |
$753 | 17,878 | - | - | - | - | - | - |
$753 17,878 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.6212 TURN OFF EQUIPMENT DURING BREAKS, REDUCE OPERATING TIME |
Savings: $2,817 Cost: - |
$2,817 | 66,530 | - | - | - | - | - | - |
$2,817 66,530 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $1,680 Cost: $2,290 |
- | - | - | - | $1,680 | 413 | - | - |
- - kWh |
- - kW-months/year |
$1,680 413 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $545 Cost: $656 |
- | - | - | - | $545 | 134 | - | - |
- - kWh |
- - kW-months/year |
$545 134 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS |
Savings: $1,070 Cost: $1,900 |
- | - | - | - | $1,070 | 262 | - | - |
- - kWh |
- - kW-months/year |
$1,070 262 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7312 MINIMIZE USE OF OUTSIDE MAKE-UP AIR FOR VENTILATION EXCEPT WHEN USED FOR ECONOMIZER CYCLE |
Savings: $7,236 Cost: $3,000 |
- | - | - | - | $7,236 | 1,778 | - | - |
- - kWh |
- - kW-months/year |
$7,236 1,778 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 3.5217 REUSE / RECYCLE/ SELL PAPER PRODUCTS |
Savings: $3,840 Cost: $150 |
- | - | - | - | - | - | $3,840 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$3,840 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 3.5316 CONTRACT A WOOD PALLET RECYCLING COMPANY |
Savings: $3,120 Cost: $100 |
- | - | - | - | - | - | $3,120 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$3,120 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $23,595 Cost: $13,685 |
$4,689 | 110,785 | $1,415 | 266 | $10,531 | 2,587 | $6,960 | - | $4,689 110,785 kWh |
$1,415 266 kW-months/year |
$10,531 2,587 MMBtu |
$6,960 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $9,124 Cost: $5,204 |
$1,119 | 26,377 | $1,415 | 266 | $2,750 | 675 | $3,840 | - | $1,119 26,377 kWh |
$1,415 266 kW-months/year |
$2,750 675 MMBtu |
$3,840 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes |