Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | West Virginia University |
---|---|
Assessment Year | 2006 |
Principal Product | photovoltaic cells and wafers |
NAICS | 334413 - Semiconductor and Related Device Manufacturing |
SIC | 3674 - Semiconductors And Related Devices |
Sales | $50,000,000-$100,000,000 |
# of Employees | 480 |
Plant Area (Sq.Ft.) | 180,000 |
Annual Production | 65 Units |
Production Hrs. Annual | 8,400 |
Location (State) | MD |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $2,900,815 | 47,183,065 | kWh | $0.06 |
Electricity Demand | $192,283 | 76,210 | kW-months/year | $2.52 |
Electricity Fees | $87,833 | - | $ | - |
Natural Gas | $77,860 | 6,106 | MMBtu | $12.75 |
TOTAL ENERGY COSTS | $3,258,791 | |||
RECOMMENDED SAVINGS* | $211,106 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $170,028 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4151 DEVELOP A REPAIR/REPLACE POLICY |
Savings: $50,956 Cost: $1,472 |
$50,850 | 802,820 | $2,890 | 1,147 | - | - | - | - | $(-2,784) | - |
$50,850 802,820 kWh |
$2,890 1,147 kW-months/year |
- - $ |
- - MMBtu |
$(-2,784) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4157 ESTABLISH A PREDICTIVE MAINTENANCE PROGRAM |
Savings: $41,030 Cost: $1,000 |
$40,680 | 642,256 | $2,312 | 917 | - | - | - | - | $(-1,962) | - |
$40,680 642,256 kWh |
$2,312 917 kW-months/year |
- - $ |
- - MMBtu |
$(-1,962) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $30,895 Cost: $15 |
$29,232 | 461,568 | $1,663 | 660 | - | - | - | - | - | - |
$29,232 461,568 kWh |
$1,663 660 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2628 UTILIZE A LESS EXPENSIVE COOLING METHOD |
Savings: $22,182 Cost: $27,387 |
$20,620 | 325,523 | $1,562 | 620 | - | - | - | - | - | - |
$20,620 325,523 kWh |
$1,562 620 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $18,000 Cost: $32,500 |
- | - | - | - | $18,000 | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$18,000 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2614 USE COOLING TOWER OR ECONOMIZER TO REPLACE CHILLER COOLING |
Savings: $16,147 Cost: $26,662 |
$16,147 | 254,910 | - | - | - | - | - | - | - | - |
$16,147 254,910 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.2625 CHILL WATER TO THE HIGHEST TEMPERATURE POSSIBLE |
Savings: $8,710 Cost: $44 |
$8,241 | 130,181 | $469 | 186 | - | - | - | - | - | - |
$8,241 130,181 kWh |
$469 186 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $6,355 Cost: $12,137 |
$6,012 | 94,917 | $343 | 136 | - | - | - | - | - | - |
$6,012 94,917 kWh |
$343 136 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $5,629 Cost: - |
$5,326 | 84,091 | $303 | 120 | - | - | - | - | - | - |
$5,326 84,091 kWh |
$303 120 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $5,177 Cost: $1,896 |
- | - | - | - | - | - | $5,177 | 406 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$5,177 406 MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $3,355 Cost: $436 |
$3,174 | 50,103 | $181 | 72 | - | - | - | - | - | - |
$3,174 50,103 kWh |
$181 72 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.2522 ISOLATE HOT OR COLD EQUIPMENT |
Savings: $1,256 Cost: $1,500 |
$1,188 | 18,752 | $68 | 27 | - | - | - | - | - | - |
$1,188 18,752 kWh |
$68 27 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $1,197 Cost: $1,811 |
$1,300 | 20,491 | $13 | 5 | - | - | - | - | $(-116) | - |
$1,300 20,491 kWh |
$13 5 kW-months/year |
- - $ |
- - MMBtu |
$(-116) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
14: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $217 Cost: $100 |
$204 | 3,000 | $13 | 5 | - | - | - | - | - | - |
$204 3,000 kWh |
$13 5 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $211,106 Cost: $106,960 |
$182,974 | 2,888,612 | $9,817 | 3,895 | $18,000 | - | $5,177 | 406 | $(-4,862) | - | $182,974 2,888,612 kWh |
$9,817 3,895 kW-months/year |
$18,000 - $ |
$5,177 406 MMBtu |
$(-4,862) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $170,028 Cost: $105,301 |
$144,109 | 2,275,111 | $7,604 | 3,017 | $18,000 | - | $5,177 | 406 | $(-4,862) | - | $144,109 2,275,111 kWh |
$7,604 3,017 kW-months/year |
$18,000 - $ |
$5,177 406 MMBtu |
$(-4,862) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes |