Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | West Virginia University |
---|---|
Assessment Year | 2007 |
Principal Product | Fans and Blowers for HVAC units |
NAICS | 333413 - Industrial and Commercial Fan and Blower and Air Purification Equipment Manufacturing |
SIC | 3564 - Blowers And Fans |
Sales | $10,000,000-$50,000,000 |
# of Employees | 107 |
Plant Area (Sq.Ft.) | 90,000 |
Annual Production | 3,000,000 Pieces |
Production Hrs. Annual | 4,000 |
Location (State) | OH |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $161,185 | 2,433,655 | kWh | $0.07 |
Electricity Demand | $66,074 | 5,260 | kW-months/year | $12.56 |
Natural Gas | $39,543 | 2,478 | MMBtu | $15.96 |
TOTAL ENERGY COSTS | $266,802 | |||
RECOMMENDED SAVINGS* | $68,335 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $43,286 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $13,251 Cost: $20,735 |
$8,440 | 127,483 | $4,811 | 383 | - | - | - | - | - | - |
$8,440 127,483 kWh |
$4,811 383 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $8,342 Cost: - |
$5,315 | 80,282 | $3,027 | 241 | - | - | - | - | - | - |
$5,315 80,282 kWh |
$3,027 241 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $7,515 Cost: $540 |
- | - | - | - | - | - | $7,515 | 471 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$7,515 471 MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $6,238 Cost: $5,148 |
$3,776 | 57,036 | $2,462 | 196 | - | - | - | - | - | - |
$3,776 57,036 kWh |
$2,462 196 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $5,696 Cost: $1,315 |
$3,823 | 57,756 | $2,173 | 173 | - | - | - | - | $(-300) | - |
$3,823 57,756 kWh |
$2,173 173 kW-months/year |
- - $ |
- - MMBtu |
$(-300) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.3191 USE DEMAND CONTROLLER OR LOAD SHEDDER |
Savings: $5,275 Cost: $7,600 |
- | - | $5,275 | 420 | - | - | - | - | - | - |
- - kWh |
$5,275 420 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4157 ESTABLISH A PREDICTIVE MAINTENANCE PROGRAM |
Savings: $4,217 Cost: $1,000 |
$3,026 | 45,708 | $1,721 | 137 | - | - | - | - | $(-530) | - |
$3,026 45,708 kWh |
$1,721 137 kW-months/year |
- - $ |
- - MMBtu |
$(-530) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $3,400 Cost: $1,050 |
$2,458 | 37,125 | $942 | 75 | - | - | - | - | - | - |
$2,458 37,125 kWh |
$942 75 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $3,252 Cost: - |
$2,071 | 31,280 | $1,181 | 94 | - | - | - | - | - | - |
$2,071 31,280 kWh |
$1,181 94 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.4151 DEVELOP A REPAIR/REPLACE POLICY |
Savings: $2,440 Cost: $898 |
$2,017 | 30,472 | $1,143 | 91 | - | - | - | - | $(-720) | - |
$2,017 30,472 kWh |
$1,143 91 kW-months/year |
- - $ |
- - MMBtu |
$(-720) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.7241 INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT |
Savings: $2,157 Cost: $1,030 |
$1,378 | 20,819 | $779 | 62 | - | - | - | - | - | - |
$1,378 20,819 kWh |
$779 62 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.2612 USE COOLING TOWER WATER INSTEAD OF REFRIGERATION |
Savings: $1,770 Cost: $5,600 |
$1,280 | 19,338 | $490 | 39 | - | - | - | - | - | - |
$1,280 19,338 kWh |
$490 39 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $1,723 Cost: $5,600 |
- | - | - | - | $1,723 | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$1,723 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
14: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $1,641 Cost: $165 |
$1,189 | 17,954 | $452 | 36 | - | - | - | - | - | - |
$1,189 17,954 kWh |
$452 36 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
15: 2.2628 UTILIZE A LESS EXPENSIVE COOLING METHOD |
Savings: $751 Cost: $1,641 |
$311 | 4,700 | $440 | 35 | - | - | - | - | - | - |
$311 4,700 kWh |
$440 35 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
16: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $667 Cost: $282 |
$483 | 7,291 | $184 | 24 | - | - | - | - | - | - |
$483 7,291 kWh |
$184 24 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $68,335 Cost: $52,604 |
$35,567 | 537,244 | $25,080 | 2,006 | $1,723 | - | $7,515 | 471 | $(-1,550) | - | $35,567 537,244 kWh |
$25,080 2,006 kW-months/year |
$1,723 - $ |
$7,515 471 MMBtu |
$(-1,550) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $43,286 Cost: $29,428 |
$28,383 | 428,725 | $15,923 | 1,277 | - | - | - | - | $(-1,020) | - | $28,383 428,725 kWh |
$15,923 1,277 kW-months/year |
- - $ |
- - MMBtu |
$(-1,020) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||