Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center West Virginia University
Assessment Year 2014
Principal Product lift trucks
NAICS 333924 - Industrial Truck, Tractor, Trailer, and Stacker Machinery Manufacturing
SIC 3537 - Industrial Trucks And Tractors
Sales $10,000,000-$50,000,000
# of Employees 200
Plant Area (Sq.Ft.) 150,000
Annual Production 840 Pieces
Production Hrs. Annual 7,280
Location (State) OH
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $385,709 7,777,200 kWh $0.05
Electricity Demand $153,150 15,315 kW-months/year $10.00
Natural Gas $230,616 55,570 MMBtu $4.15
TOTAL ENERGY COSTS $769,475
RECOMMENDED SAVINGS* $99,672 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $22,600
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas
$ kWh $ kW-months/year $ MMBtu
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$38,596
Cost:
$58,450
$28,966 584,002 $9,630 963 - - $28,966
584,002
kWh
$9,630
963
kW-months/year
-
-
MMBtu
02: 2.2492 USE "HEAT WHEEL" OR OTHER HEAT EXCHANGER TO CROSS-EXCHANGE BUILDING EXHAUST AIR WITH MAKE-UP AIR Savings:
$24,659
Cost:
$51,000
- - - - $24,659 5,942 -
-
kWh
-
-
kW-months/year
$24,659
5,942
MMBtu
03: 2.4224 UPGRADE CONTROLS ON COMPRESSORS Savings:
$11,868
Cost:
$7,750
$8,648 174,355 $3,220 322 - - $8,648
174,355
kWh
$3,220
322
kW-months/year
-
-
MMBtu
04: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS Savings:
$6,987
Cost:
$3,690
$(-481) (-9,703) $(-230) (-23) $7,698 1,855 $(-481)
(-9,703)
kWh
$(-230)
(-23)
kW-months/year
$7,698
1,855
MMBtu
05: 2.3191 USE DEMAND CONTROLLER OR LOAD SHEDDER Savings:
$6,830
Cost:
$5,600
- - $6,830 683 - - -
-
kWh
$6,830
683
kW-months/year
-
-
MMBtu
06: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE Savings:
$4,252
Cost:
$4,500
$3,192 64,350 $1,060 106 - - $3,192
64,350
kWh
$1,060
106
kW-months/year
-
-
MMBtu
07: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$2,693
Cost:
$468
$2,023 40,786 $670 67 - - $2,023
40,786
kWh
$670
67
kW-months/year
-
-
MMBtu
08: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$2,298
Cost:
-
$1,728 34,836 $570 57 - - $1,728
34,836
kWh
$570
57
kW-months/year
-
-
MMBtu
09: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$1,489
Cost:
$6,113
$949 19,133 $540 54 - - $949
19,133
kWh
$540
54
kW-months/year
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$99,672
Cost:
$137,571
$45,025 907,759 $22,290 2,229 $32,357 7,797 $45,025
907,759
kWh
$22,290
2,229
kW-months/year
$32,357
7,797
MMBtu
TOTAL IMPLEMENTED Savings:
$22,600
Cost:
$18,831
$16,540 333,460 $6,060 606 - - $16,540
333,460
kWh
$6,060
606
kW-months/year
-
-
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ MMBtu
Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas