Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | West Virginia University |
---|---|
Assessment Year | 2014 |
Principal Product | polymer pellets |
NAICS | 325211 - Plastics Material and Resin Manufacturing |
SIC | 2821 - Plastics Materials And Resins |
Sales | $1,000,000-$5,000,000 |
# of Employees | 63 |
Plant Area (Sq.Ft.) | 217,000 |
Annual Production | 4,800,000 Pounds |
Production Hrs. Annual | 8,568 |
Location (State) | WV |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $300,498 | 7,924,800 | kWh | $0.04 |
Electricity Demand | $260,973 | 19,760 | kW-months/year | $13.21 |
Electricity Fees | $12,225 | - | $ | - |
TOTAL ENERGY COSTS | $573,696 | |||
RECOMMENDED SAVINGS* | $99,870 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $91,318 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Personnel Changes | Electricity Usage | Electricity Demand | Personnel Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $40,956 Cost: $44,486 |
$27,891 | 706,102 | $13,065 | 989 | - | - |
$27,891 706,102 kWh |
$13,065 989 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.3191 USE DEMAND CONTROLLER OR LOAD SHEDDER |
Savings: $19,168 Cost: $5,300 |
- | - | $19,168 | 1,451 | - | - |
- - kWh |
$19,168 1,451 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $8,848 Cost: $509 |
$6,021 | 152,443 | $2,827 | 214 | - | - |
$6,021 152,443 kWh |
$2,827 214 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4157 ESTABLISH A PREDICTIVE MAINTENANCE PROGRAM |
Savings: $5,786 Cost: $1,000 |
$4,983 | 126,160 | $2,338 | 177 | $(-1,535) | - |
$4,983 126,160 kWh |
$2,338 177 kW-months/year |
$(-1,535) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4224 UPGRADE CONTROLS ON COMPRESSORS |
Savings: $5,218 Cost: $10,000 |
$3,554 | 89,964 | $1,664 | 126 | - | - |
$3,554 89,964 kWh |
$1,664 126 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $5,192 Cost: $7,244 |
$3,237 | 81,945 | $1,955 | 148 | - | - |
$3,237 81,945 kWh |
$1,955 148 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $5,090 Cost: - |
$3,465 | 87,719 | $1,625 | 123 | - | - |
$3,465 87,719 kWh |
$1,625 123 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $3,507 Cost: $1,251 |
$2,384 | 60,358 | $1,123 | 85 | - | - |
$2,384 60,358 kWh |
$1,123 85 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $2,643 Cost: $15 |
$1,798 | 45,508 | $845 | 64 | - | - |
$1,798 45,508 kWh |
$845 64 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $2,071 Cost: $1,000 |
$1,410 | 35,690 | $661 | 50 | - | - |
$1,410 35,690 kWh |
$661 50 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.4151 DEVELOP A REPAIR/REPLACE POLICY |
Savings: $1,391 Cost: $661 |
$1,196 | 30,278 | $555 | 42 | $(-360) | - |
$1,196 30,278 kWh |
$555 42 kW-months/year |
$(-360) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $99,870 Cost: $71,466 |
$55,939 | 1,416,167 | $45,826 | 3,469 | $(-1,895) | - | $55,939 1,416,167 kWh |
$45,826 3,469 kW-months/year |
$(-1,895) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $91,318 Cost: $69,805 |
$49,868 | 1,262,480 | $42,985 | 3,254 | $(-1,535) | - | $49,868 1,262,480 kWh |
$42,985 3,254 kW-months/year |
$(-1,535) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Personnel Changes | Electricity Usage | Electricity Demand | Personnel Changes |