Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | West Virginia University |
---|---|
Assessment Year | 2018 |
Principal Product | Nuts, Bolts and Screws |
NAICS | 332722 - Bolt, Nut, Screw, Rivet, and Washer Manufacturing |
SIC | 3452 - Bolts, Nuts, Rivets, And Washers |
Sales | $5,000,000-$10,000,000 |
# of Employees | 10 |
Plant Area (Sq.Ft.) | 200,000 |
Annual Production | 480,000 Units |
Production Hrs. Annual | 2,040 |
Location (State) | WV |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $76,850 | 1,088,744 | kWh | $0.07 |
Electricity Demand | $33,271 | 4,674 | kW-months/year | $7.12 |
Natural Gas | $108,555 | 14,418 | MMBtu | $7.53 |
TOTAL ENERGY COSTS | $219,043 | |||
RECOMMENDED SAVINGS* | $29,196 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $27,943 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Water Usage | Water Disposal | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Water Usage | Water Disposal | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | $ | Tgal | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.6232 INSTALL SET-BACK TIMERS |
Savings: $15,007 Cost: $2,522 |
$1,641 | 23,244 | - | - | $13,366 | 1,775 | - | - | - | - | - | - |
$1,641 23,244 kWh |
- - kW-months/year |
$13,366 1,775 MMBtu |
- - Tgal |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $8,102 Cost: $13,629 |
$5,603 | 79,360 | $2,499 | 351 | - | - | - | - | - | - | - | - |
$5,603 79,360 kWh |
$2,499 351 kW-months/year |
- - MMBtu |
- - Tgal |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $1,765 Cost: $1,784 |
$1,110 | 15,721 | $655 | 92 | - | - | - | - | - | - | - | - |
$1,110 15,721 kWh |
$655 92 kW-months/year |
- - MMBtu |
- - Tgal |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $1,742 Cost: $171 |
$1,094 | 15,492 | $648 | 91 | - | - | - | - | - | - | - | - |
$1,094 15,492 kWh |
$648 91 kW-months/year |
- - MMBtu |
- - Tgal |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.3131 RESCHEDULE PLANT OPERATIONS OR REDUCE LOAD TO AVOID PEAKS |
Savings: $1,253 Cost: $6,000 |
- | - | $1,253 | 176 | - | - | - | - | - | - | - | - |
- - kWh |
$1,253 176 kW-months/year |
- - MMBtu |
- - Tgal |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 3.4151 MINIMIZE WATER USAGE |
Savings: $535 Cost: $1,400 |
- | - | - | - | - | - | $245 | 41 | $367 | 41 | $(-77) | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$245 41 Tgal |
$367 41 Tgal |
$(-77) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4151 DEVELOP A REPAIR/REPLACE POLICY |
Savings: $471 Cost: $696 |
$466 | 6,605 | $278 | 39 | - | - | - | - | - | - | $(-273) | - |
$466 6,605 kWh |
$278 39 kW-months/year |
- - MMBtu |
- - Tgal |
- - Tgal |
$(-273) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $321 Cost: $34 |
$200 | 2,828 | $121 | 17 | - | - | - | - | - | - | - | - |
$200 2,828 kWh |
$121 17 kW-months/year |
- - MMBtu |
- - Tgal |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $29,196 Cost: $26,236 |
$10,114 | 143,250 | $5,454 | 766 | $13,366 | 1,775 | $245 | 41 | $367 | 41 | $(-350) | - | $10,114 143,250 kWh |
$5,454 766 kW-months/year |
$13,366 1,775 MMBtu |
$245 41 Tgal |
$367 41 Tgal |
$(-350) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $27,943 Cost: $20,236 |
$10,114 | 143,250 | $4,201 | 590 | $13,366 | 1,775 | $245 | 41 | $367 | 41 | $(-350) | - | $10,114 143,250 kWh |
$4,201 590 kW-months/year |
$13,366 1,775 MMBtu |
$245 41 Tgal |
$367 41 Tgal |
$(-350) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | $ | Tgal | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Water Usage | Water Disposal | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Water Usage | Water Disposal | Administrative Changes |