Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Bradley University |
---|---|
Assessment Year | 1996 |
Principal Product | corrugated shipping containers |
NAICS | n/a |
SIC | 2653 - Corrugated And Solid Fiber Boxes |
Sales | $5,000,000-$10,000,000 |
# of Employees | 47 |
Plant Area (Sq.Ft.) | 73,875 |
Annual Production | 100,000 Thousand Feet |
Production Hrs. Annual | 6,240 |
Location (State) | IL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $41,071 | 639,508 | kWh | $0.06 |
Electricity Demand | $5,460 | 2,184 | kW-months/year | $2.50 |
Electricity Fees | $1,847 | - | $ | - |
Natural Gas | $5,274 | 1,504 | MMBtu | $3.51 |
TOTAL ENERGY COSTS | $90,272 | |||
RECOMMENDED SAVINGS* | $21,462 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $4,116 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Solid Waste (non-haz) | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Solid Waste (non-haz) | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | $ | lb | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $1,808 Cost: $375 |
$1,568 | 40,152 | $240 | 96 | - | - | - | - | - | - |
$1,568 40,152 kWh |
$240 96 kW-months/year |
- - MMBtu |
- - Tgal |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $1,366 Cost: $3,420 |
$1,246 | 31,946 | $120 | 46 | - | - | - | - | - | - |
$1,246 31,946 kWh |
$120 46 kW-months/year |
- - MMBtu |
- - Tgal |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $870 Cost: $40 |
$817 | 21,102 | $53 | 21 | - | - | - | - | - | - |
$817 21,102 kWh |
$53 21 kW-months/year |
- - MMBtu |
- - Tgal |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $656 Cost: $525 |
$586 | 15,240 | $70 | 28 | - | - | - | - | - | - |
$586 15,240 kWh |
$70 28 kW-months/year |
- - MMBtu |
- - Tgal |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $618 Cost: $500 |
- | - | - | - | $618 | 177 | - | - | - | - |
- - kWh |
- - kW-months/year |
$618 177 MMBtu |
- - Tgal |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $194 Cost: $300 |
$182 | 4,689 | $12 | 5 | - | - | - | - | - | - |
$182 4,689 kWh |
$12 5 kW-months/year |
- - MMBtu |
- - Tgal |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $130 Cost: $301 |
$119 | 3,224 | $11 | 4 | - | - | - | - | - | - |
$119 3,224 kWh |
$11 4 kW-months/year |
- - MMBtu |
- - Tgal |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 3.4113 TREAT AND REUSE RINSE WATERS |
Savings: $13,620 Cost: $15,000 |
- | - | - | - | - | - | $13,620 | - | - | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$13,620 - Tgal |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 3.6122 INSTALL SOLID WASTE INCINERATOR FOR HEAT |
Savings: $2,200 Cost: - |
- | - | - | - | - | - | - | - | $2,200 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
- - Tgal |
$2,200 - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $21,462 Cost: $20,461 |
$4,518 | 116,353 | $506 | 200 | $618 | 177 | $13,620 | - | $2,200 | - | $4,518 116,353 kWh |
$506 200 kW-months/year |
$618 177 MMBtu |
$13,620 - Tgal |
$2,200 - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $4,116 Cost: $4,896 |
$3,115 | 80,011 | $383 | 151 | $618 | 177 | - | - | - | - | $3,115 80,011 kWh |
$383 151 kW-months/year |
$618 177 MMBtu |
- - Tgal |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | $ | lb | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Solid Waste (non-haz) | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Solid Waste (non-haz) |