Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Bradley University
Assessment Year 1996
Principal Product Corrugated Roofing and Siding Panels
NAICS n/a
SIC 3444 - Sheet Metalwork
Sales n/a
# of Employees 34
Plant Area (Sq.Ft.) 93,200
Annual Production 45,000,000 Pounds
Production Hrs. Annual 2,080
Location (State) IL
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $54,754 1,105,510 kWh $0.05
Electricity Demand $37,503 4,448 kW-months/year $8.43
Electricity Fees $9,428 - $ -
TOTAL ENERGY COSTS $102,585
RECOMMENDED SAVINGS* $22,863 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $6,772
#|Description Savings
Cost
Status Electricity Usage Electricity Demand LPG By-product Production Electricity Usage Electricity Demand LPG By-product Production
$ kWh $ kW-months/year $ MMBtu $ $
01: 2.1311 REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT Savings:
$15,772
Cost:
$17,505
$20,150 429,660 $9,352 1,336 $(-13,730) (-1,725) - - $20,150
429,660
kWh
$9,352
1,336
kW-months/year
$(-13,730)
(-1,725)
MMBtu
-
-
$
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$2,463
Cost:
$5,801
$1,241 26,377 $1,222 145 - - - - $1,241
26,377
kWh
$1,222
145
kW-months/year
-
-
MMBtu
-
-
$
03: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$1,346
Cost:
$4,140
$668 14,361 $678 81 - - - - $668
14,361
kWh
$678
81
kW-months/year
-
-
MMBtu
-
-
$
04: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$450
Cost:
$375
$231 4,982 $219 26 - - - - $231
4,982
kWh
$219
26
kW-months/year
-
-
MMBtu
-
-
$
05: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$353
Cost:
$300
$228 4,982 $125 15 - - - - $228
4,982
kWh
$125
15
kW-months/year
-
-
MMBtu
-
-
$
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$319
Cost:
$504
$256 5,569 $63 8 - - - - $256
5,569
kWh
$63
8
kW-months/year
-
-
MMBtu
-
-
$
07: 3.5316 CONTRACT A WOOD PALLET RECYCLING COMPANY Savings:
$2,160
Cost:
$370
- - - - - - $2,160 - -
-
kWh
-
-
kW-months/year
-
-
MMBtu
$2,160
-
$
TOTAL RECOMMENDED Savings:
$22,863
Cost:
$28,995
$22,774 485,931 $11,659 1,611 $(-13,730) (-1,725) $2,160 - $22,774
485,931
kWh
$11,659
1,611
kW-months/year
$(-13,730)
(-1,725)
MMBtu
$2,160
-
$
TOTAL IMPLEMENTED Savings:
$6,772
Cost:
$10,986
$2,368 50,702 $2,244 267 - - $2,160 - $2,368
50,702
kWh
$2,244
267
kW-months/year
-
-
MMBtu
$2,160
-
$
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ $
Electricity Usage Electricity Demand LPG By-product Production Electricity Usage Electricity Demand LPG By-product Production