Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Bradley University |
---|---|
Assessment Year | 1996 |
Principal Product | Paper Products |
NAICS | n/a |
SIC | 2671 - Paper Coated & Laminated, Packaging |
Sales | $10,000,000-$50,000,000 |
# of Employees | 89 |
Plant Area (Sq.Ft.) | 98,940 |
Annual Production | 2,147,483,647 Thousand Feet |
Production Hrs. Annual | 7,488 |
Location (State) | IL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $120,662 | 3,892,732 | kWh | $0.03 |
Electricity Demand | $88,928 | 6,973 | kW-months/year | $12.75 |
Electricity Fees | $2,852 | - | $ | - |
Natural Gas | $146,661 | 39,887 | MMBtu | $3.68 |
TOTAL ENERGY COSTS | $385,903 | |||
RECOMMENDED SAVINGS* | $27,964 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $13,965 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Personnel Changes | Ancillary Material Cost | Water Consumption | Electricity Usage | Electricity Demand | Personnel Changes | Ancillary Material Cost | Water Consumption | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | $ | Tgal | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $7,122 Cost: $12,270 |
$4,754 | 153,283 | $2,368 | 186 | - | - | - | - | - | - |
$4,754 153,283 kWh |
$2,368 186 kW-months/year |
- - $ |
- - $ |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $2,590 Cost: $800 |
$1,548 | 49,824 | $1,042 | 82 | - | - | - | - | - | - |
$1,548 49,824 kWh |
$1,042 82 kW-months/year |
- - $ |
- - $ |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $1,611 Cost: $2,563 |
$856 | 27,550 | $755 | 59 | - | - | - | - | - | - |
$856 27,550 kWh |
$755 59 kW-months/year |
- - $ |
- - $ |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $1,441 Cost: $1,500 |
$551 | 17,878 | $890 | 70 | - | - | - | - | - | - |
$551 17,878 kWh |
$890 70 kW-months/year |
- - $ |
- - $ |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $1,531 Cost: $2,590 |
$773 | 24,912 | $510 | 40 | $34 | - | $214 | - | - | - |
$773 24,912 kWh |
$510 40 kW-months/year |
$34 - $ |
$214 - $ |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $1,111 Cost: $1,020 |
$742 | 24,033 | $369 | 29 | - | - | - | - | - | - |
$742 24,033 kWh |
$369 29 kW-months/year |
- - $ |
- - $ |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7243 IMPROVE AIR CIRCULATION WITH DESTRATIFICATION FANS / OTHER METHODS |
Savings: $562 Cost: $660 |
- | - | $562 | 55 | - | - | - | - | - | - |
- - kWh |
$562 55 kW-months/year |
- - $ |
- - $ |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 3.3122 USE FILTRATION, CENTRIFUGING TO REMOVE CONTAMINANTS |
Savings: $11,996 Cost: $9,045 |
$(-350) | (-11,430) | - | - | $1,680 | - | - | - | $10,666 | - |
$(-350) (-11,430) kWh |
- - kW-months/year |
$1,680 - $ |
- - $ |
$10,666 - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $27,964 Cost: $30,448 |
$8,874 | 286,050 | $6,496 | 521 | $1,714 | - | $214 | - | $10,666 | - | $8,874 286,050 kWh |
$6,496 521 kW-months/year |
$1,714 - $ |
$214 - $ |
$10,666 - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $13,965 Cost: $19,243 |
$8,673 | 279,602 | $5,044 | 396 | $34 | - | $214 | - | - | - | $8,673 279,602 kWh |
$5,044 396 kW-months/year |
$34 - $ |
$214 - $ |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | $ | Tgal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Personnel Changes | Ancillary Material Cost | Water Consumption | Electricity Usage | Electricity Demand | Personnel Changes | Ancillary Material Cost | Water Consumption |