IAC logo
IAC Assessment: BD0205
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: BD0205
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Bradley University
Assessment Year 2002
Principal Product Diesel Engine Filters
NAICS n/a
SIC 3599 - Industrial Machinery, Nec
Sales $50,000,000-$100,000,000
# of Employees 185
Plant Area (Sq.Ft.) 228,000
Annual Production 10,500,000 Pieces
Production Hrs. Annual 8,760
Location (State) IL
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $408,876 12,325,568 kWh $0.03
Electricity Demand $220,901 22,780 kW-months/year $9.70
Electricity Fees $72,632 - $ -
Natural Gas $397,233 87,399 MMBtu $4.55
TOTAL ENERGY COSTS $1,103,704
RECOMMENDED SAVINGS* $173,736 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $6,829
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas One-time Revenue or Avoided Cost Electricity Usage Electricity Demand Natural Gas One-time Revenue or Avoided Cost
$ kWh $ kW-months/year $ MMBtu $ $
01: 2.2426 USE WASTE HEAT FROM FLUE GASES TO HEAT SPACE CONDITIONING AIR Savings:
$133,965
Cost:
$75,270
- - - - $133,965 29,770 - - -
-
kWh
-
-
kW-months/year
$133,965
29,770
MMBtu
-
-
$
02: 2.7231 USE RADIANT HEATER FOR SPOT HEATING Savings:
$25,105
Cost:
$60,000
- - - - $25,105 5,579 - - -
-
kWh
-
-
kW-months/year
$25,105
5,579
MMBtu
-
-
$
03: 2.1123 INSTALL AUTOMATIC STACK DAMPER Savings:
$4,550
Cost:
$5,000
- - - - $4,550 1,011 - - -
-
kWh
-
-
kW-months/year
$4,550
1,011
MMBtu
-
-
$
04: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$3,089
Cost:
$4,800
$2,371 71,647 $718 74 - - - - $2,371
71,647
kWh
$718
74
kW-months/year
-
-
MMBtu
-
-
$
05: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$2,003
Cost:
$1,000
$1,429 43,183 $574 59 - - - - $1,429
43,183
kWh
$574
59
kW-months/year
-
-
MMBtu
-
-
$
06: 2.2426 USE WASTE HEAT FROM FLUE GASES TO HEAT SPACE CONDITIONING AIR Savings:
$1,411
Cost:
$1,500
- - - - $1,411 314 - - -
-
kWh
-
-
kW-months/year
$1,411
314
MMBtu
-
-
$
07: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$1,387
Cost:
$300
$990 29,911 $397 41 - - - - $990
29,911
kWh
$397
41
kW-months/year
-
-
MMBtu
-
-
$
08: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$1,324
Cost:
$1,425
$716 21,620 $608 63 - - - - $716
21,620
kWh
$608
63
kW-months/year
-
-
MMBtu
-
-
$
09: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$552
Cost:
$800
$377 11,378 $175 18 - - - - $377
11,378
kWh
$175
18
kW-months/year
-
-
MMBtu
-
-
$
10: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$350
Cost:
$360
$132 3,995 $53 6 - - $165 - $132
3,995
kWh
$53
6
kW-months/year
-
-
MMBtu
$165
-
$
TOTAL RECOMMENDED Savings:
$173,736
Cost:
$150,455
$6,015 181,734 $2,525 261 $165,031 36,674 $165 - $6,015
181,734
kWh
$2,525
261
kW-months/year
$165,031
36,674
MMBtu
$165
-
$
TOTAL IMPLEMENTED Savings:
$6,829
Cost:
$6,460
$4,922 148,736 $1,742 180 - - $165 - $4,922
148,736
kWh
$1,742
180
kW-months/year
-
-
MMBtu
$165
-
$
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ $
Electricity Usage Electricity Demand Natural Gas One-time Revenue or Avoided Cost Electricity Usage Electricity Demand Natural Gas One-time Revenue or Avoided Cost