Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Bradley University |
---|---|
Assessment Year | 2014 |
Principal Product | Plastic resin pellets |
NAICS | 488991 - Packing and Crating |
SIC | 4783 - Packing And Crating |
Sales | $100,000,000-$500,000,000 |
# of Employees | 250 |
Plant Area (Sq.Ft.) | 323,700 |
Annual Production | 0 Units |
Production Hrs. Annual | 5,200 |
Location (State) | IL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $281,480 | 2,663,579 | kWh | $0.11 |
Natural Gas | $120,525 | 14,142 | MMBtu | $8.52 |
LPG | $59,953 | 2,910 | MMBtu | $20.60 |
Fuel Oil #2 | $325,204 | 13,515 | MMBtu | $24.06 |
Other Gas | $22,891 | 861 | MMBtu | $26.59 |
TOTAL ENERGY COSTS | $810,053 | |||
RECOMMENDED SAVINGS* | $47,546 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $7,471 |
#|Description |
Savings Cost |
Status | Electricity Usage | Natural Gas | Personnel Changes | Ancillary Material Cost | Electricity Usage | Natural Gas | Personnel Changes | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | MMBtu | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7231 USE RADIANT HEATER FOR SPOT HEATING |
Savings: $19,966 Cost: $27,000 |
- | - | $19,966 | 2,343 | - | - | - | - |
- - kWh |
$19,966 2,343 MMBtu |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $16,234 Cost: $24,940 |
$15,981 | 151,204 | - | - | $119 | - | $134 | - |
$15,981 151,204 kWh |
- - MMBtu |
$119 - $ |
$134 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $2,837 Cost: $1,000 |
$2,837 | 26,844 | - | - | - | - | - | - |
$2,837 26,844 kWh |
- - MMBtu |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4321 UPGRADE OBSOLETE EQUIPMENT |
Savings: $2,486 Cost: $20 |
$2,486 | 23,522 | - | - | - | - | - | - |
$2,486 23,522 kWh |
- - MMBtu |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $2,148 Cost: $2,850 |
$2,105 | 19,918 | - | - | $12 | - | $31 | - |
$2,105 19,918 kWh |
- - MMBtu |
$12 - $ |
$31 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $1,909 Cost: $1,025 |
$1,372 | 12,982 | - | - | $225 | - | $312 | - |
$1,372 12,982 kWh |
- - MMBtu |
$225 - $ |
$312 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $777 Cost: $450 |
$659 | 6,234 | - | - | $104 | - | $14 | - |
$659 6,234 kWh |
- - MMBtu |
$104 - $ |
$14 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $461 Cost: $320 |
$461 | 4,357 | - | - | - | - | - | - |
$461 4,357 kWh |
- - MMBtu |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $406 Cost: $750 |
$406 | 3,840 | - | - | - | - | - | - |
$406 3,840 kWh |
- - MMBtu |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $322 Cost: $143 |
$254 | 2,402 | - | - | $19 | - | $49 | - |
$254 2,402 kWh |
- - MMBtu |
$19 - $ |
$49 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $47,546 Cost: $58,498 |
$26,561 | 251,303 | $19,966 | 2,343 | $479 | - | $540 | - | $26,561 251,303 kWh |
$19,966 2,343 MMBtu |
$479 - $ |
$540 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $7,471 Cost: $3,870 |
$7,428 | 70,284 | - | - | $12 | - | $31 | - | $7,428 70,284 kWh |
- - MMBtu |
$12 - $ |
$31 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | MMBtu | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Natural Gas | Personnel Changes | Ancillary Material Cost | Electricity Usage | Natural Gas | Personnel Changes | Ancillary Material Cost |