Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Georgia Institute of Technology
Assessment Year 1986
Principal Product SPUN CARPET YARN
NAICS n/a
SIC 2281 - Yarn Spinning Mills
Sales $10,000,000-$50,000,000
# of Employees 130
Plant Area (Sq.Ft.) 0
Annual Production 7,600,000 Pounds
Production Hrs. Annual 6,000
Location (State) GA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $491,621 9,842,908 kWh $0.05
Natural Gas $168,648 40,947 MMBtu $4.12
Fuel Oil #2 $5,673 1,589 MMBtu $3.57
TOTAL ENERGY COSTS $665,942
RECOMMENDED SAVINGS* $263,636 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Natural Gas Fuel Oil #2 Electricity Usage Natural Gas Fuel Oil #2
$ kWh $ MMBtu $ MMBtu
01: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$2,170
Cost:
$2,356
$2,170 43,376 - - - - $2,170
43,376
kWh
-
-
MMBtu
-
-
MMBtu
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$11,783
Cost:
$32,572
$11,783 235,639 - - - - $11,783
235,639
kWh
-
-
MMBtu
-
-
MMBtu
03: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$1,882
Cost:
$2,790
$1,882 37,515 - - - - $1,882
37,515
kWh
-
-
MMBtu
-
-
MMBtu
04: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO Savings:
$10,257
Cost:
$1,000
- - $9,925 2,409 $332 93 -
-
kWh
$9,925
2,409
MMBtu
$332
93
MMBtu
05: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$1,970
Cost:
-
$1,970 39,273 - - - - $1,970
39,273
kWh
-
-
MMBtu
-
-
MMBtu
06: 2.7226 USE COMPUTER PROGRAMS TO OPTIMIZE HVAC PERFORMANCE Savings:
$61,200
Cost:
$10,000
$61,200 1,224,209 - - - - $61,200
1,224,209
kWh
-
-
MMBtu
-
-
MMBtu
07: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES Savings:
$37,018
Cost:
$91,200
- - $35,815 8,693 $1,203 337 -
-
kWh
$35,815
8,693
MMBtu
$1,203
337
MMBtu
08: 2.4312 IMPROVE LUBRICATION PRACTICES Savings:
$10,261
Cost:
-
$10,261 205,158 - - - - $10,261
205,158
kWh
-
-
MMBtu
-
-
MMBtu
09: 2.1333 CONVERT COMBUSTION EQUIPMENT TO BURN OIL Savings:
$127,095
Cost:
$28,000
- - $122,961 29,845 $4,134 1,158 -
-
kWh
$122,961
29,845
MMBtu
$4,134
1,158
MMBtu
TOTAL RECOMMENDED Savings:
$263,636
Cost:
$167,918
$89,266 1,785,170 $168,701 40,947 $5,669 1,588 $89,266
1,785,170
kWh
$168,701
40,947
MMBtu
$5,669
1,588
MMBtu
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - -
-
kWh
-
-
MMBtu
-
-
MMBtu
Savings
Cost
$ kWh $ MMBtu $ MMBtu
Electricity Usage Natural Gas Fuel Oil #2 Electricity Usage Natural Gas Fuel Oil #2