IAC logo
IAC Assessment: IA0399
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: IA0399
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Iowa State University
Assessment Year 2006
Principal Product
NAICS n/a
SIC n/a
Sales n/a
# of Employees 0
Plant Area (Sq.Ft.) 0
Annual Production 0 Units
Production Hrs. Annual 0
Location (State) MN
Source Yearly Cost Usage Unit Unit Cost
TOTAL ENERGY COSTS -
RECOMMENDED SAVINGS* $694,018 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $12,856
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas
$ kWh $ kW-months/year $ MMBtu
01: 2.1336 INSTALL EQUIPMENT TO UTILIZE WASTE FUEL Savings:
$608,664
Cost:
$200,000
- - - - $608,664 82,252 -
-
kWh
-
-
kW-months/year
$608,664
82,252
MMBtu
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$3,793
Cost:
$6,686
$3,017 73,944 $776 103 - - $3,017
73,944
kWh
$776
103
kW-months/year
-
-
MMBtu
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$1,887
Cost:
$1,236
$1,500 36,759 $387 51 - - $1,500
36,759
kWh
$387
51
kW-months/year
-
-
MMBtu
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$6,559
Cost:
$2,000
$5,215 127,834 $1,344 179 - - $5,215
127,834
kWh
$1,344
179
kW-months/year
-
-
MMBtu
05: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$1,063
Cost:
$100
$857 21,006 $206 30 - - $857
21,006
kWh
$206
30
kW-months/year
-
-
MMBtu
06: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED Savings:
$6,594
Cost:
$2,000
$5,243 128,520 $1,351 180 - - $5,243
128,520
kWh
$1,351
180
kW-months/year
-
-
MMBtu
07: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$786
Cost:
$150
$625 15,336 $161 21 - - $625
15,336
kWh
$161
21
kW-months/year
-
-
MMBtu
08: 2.1213 DIRECT WARMEST AIR TO COMBUSTION INTAKE Savings:
$5,439
Cost:
$600
- - - - $5,439 735 -
-
kWh
-
-
kW-months/year
$5,439
735
MMBtu
09: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO Savings:
$45,645
Cost:
$2,000
- - - - $45,645 6,114 -
-
kWh
-
-
kW-months/year
$45,645
6,114
MMBtu
10: 2.2135 REPAIR AND ELIMINATE STEAM LEAKS Savings:
$6,297
Cost:
$1,500
- - - - $6,297 851 -
-
kWh
-
-
kW-months/year
$6,297
851
MMBtu
11: 2.7442 KEEP DOORS AND WINDOWS SHUT WHEN NOT ON USE Savings:
$4,276
Cost:
$6,000
$4,276 104,810 - - - - $4,276
104,810
kWh
-
-
kW-months/year
-
-
MMBtu
12: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS Savings:
$1,219
Cost:
$340
$1,219 29,886 - - - - $1,219
29,886
kWh
-
-
kW-months/year
-
-
MMBtu
13: 2.2696 USE EXCESS COLD PROCESS FLUID FOR INDUSTRIAL COOLING NEEDS Savings:
$1,311
Cost:
$1,960
$1,042 25,533 $269 35 - - $1,042
25,533
kWh
$269
35
kW-months/year
-
-
MMBtu
14: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$485
Cost:
$566
$386 9,000 $99 1 - - $386
9,000
kWh
$99
1
kW-months/year
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$694,018
Cost:
$225,138
$23,380 572,628 $4,593 600 $666,045 89,952 $23,380
572,628
kWh
$4,593
600
kW-months/year
$666,045
89,952
MMBtu
TOTAL IMPLEMENTED Savings:
$12,856
Cost:
$3,500
$5,215 127,834 $1,344 179 $6,297 851 $5,215
127,834
kWh
$1,344
179
kW-months/year
$6,297
851
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ MMBtu
Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas