Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Illinois, Chicago |
---|---|
Assessment Year | 2007 |
Principal Product | Fuel and Oil Filters |
NAICS | 336390 - Other Motor Vehicle Parts Manufacturing |
SIC | 2679 - Converted Paper Products, Nec |
Sales | $100,000,000-$500,000,000 |
# of Employees | 438 |
Plant Area (Sq.Ft.) | 211,360 |
Annual Production | 12,000,000 Pieces |
Production Hrs. Annual | 6,744 |
Location (State) | WI |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $522,717 | 11,725,746 | kWh | $0.04 |
Electricity Demand | $285,306 | 30,980 | kW-months/year | $9.21 |
Natural Gas | $290,981 | 33,989 | MMBtu | $8.56 |
TOTAL ENERGY COSTS | $1,156,639 | |||
RECOMMENDED SAVINGS* | $44,082 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $6,415 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Ancillary Material Cost | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $2,802 Cost: $9,080 |
$1,573 | 34,169 | $682 | 74 | - | - | - | - | $547 | - |
$1,573 34,169 kWh |
$682 74 kW-months/year |
- - $ |
- - MMBtu |
$547 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $2,224 Cost: $5,038 |
$2,043 | 44,409 | $181 | 20 | - | - | - | - | - | - |
$2,043 44,409 kWh |
$181 20 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $2,294 Cost: $5,851 |
$1,658 | 36,041 | $636 | 69 | - | - | - | - | - | - |
$1,658 36,041 kWh |
$636 69 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $1,389 Cost: $3,105 |
$1,389 | 30,187 | - | - | - | - | - | - | - | - |
$1,389 30,187 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT |
Savings: $3,287 Cost: $17,000 |
- | - | - | - | - | - | $3,287 | 384 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$3,287 384 MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7314 REDUCE VENTILATION AIR |
Savings: $23,044 Cost: - |
- | - | - | - | - | - | $23,044 | 2,692 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$23,044 2,692 MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.3132 RECHARGE BATTERIES ON DURING OFF-PEAK DEMAND PERIODS |
Savings: $9,042 Cost: $26,000 |
- | - | - | - | $9,042 | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$9,042 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $44,082 Cost: $66,074 |
$6,663 | 144,806 | $1,499 | 163 | $9,042 | - | $26,331 | 3,076 | $547 | - | $6,663 144,806 kWh |
$1,499 163 kW-months/year |
$9,042 - $ |
$26,331 3,076 MMBtu |
$547 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $6,415 Cost: $17,223 |
$5,005 | 108,765 | $863 | 94 | - | - | - | - | $547 | - | $5,005 108,765 kWh |
$863 94 kW-months/year |
- - $ |
- - MMBtu |
$547 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Ancillary Material Cost | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Ancillary Material Cost |