Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Univ. of Kansas
Assessment Year 1985
Principal Product NOVELTY ICE CREAM & ICE
NAICS n/a
SIC 2024 - Ice Cream And Frozen Desserts
Sales $10,000,000-$50,000,000
# of Employees 150
Plant Area (Sq.Ft.) 0
Annual Production 20,000,000 Pieces
Production Hrs. Annual 7,200
Location (State) MO
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $639,674 14,917,937 kWh $0.04
Natural Gas $173,393 42,375 MMBtu $4.09
TOTAL ENERGY COSTS $813,067
RECOMMENDED SAVINGS* $92,335 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $75,513
#|Description Savings
Cost
Status Electricity Usage Natural Gas Administrative Changes Electricity Usage Natural Gas Administrative Changes
$ kWh $ MMBtu $ $
01: 2.2121 INCREASE AMOUNT OF CONDENSATE RETURNED Savings:
$28,837
Cost:
$33,000
- - $13,337 3,261 $15,500 - -
-
kWh
$13,337
3,261
MMBtu
$15,500
-
$
02: 2.2447 HEAT WATER WITH EXHAUST HEAT Savings:
$20,949
Cost:
$37,000
- - $20,949 5,122 - - -
-
kWh
$20,949
5,122
MMBtu
-
-
$
03: 2.3191 USE DEMAND CONTROLLER OR LOAD SHEDDER Savings:
$16,822
Cost:
$9,000
$16,822 - - - - - $16,822
-
kWh
-
-
MMBtu
-
-
$
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$7,248
Cost:
$4,815
$7,248 169,109 - - - - $7,248
169,109
kWh
-
-
MMBtu
-
-
$
05: 2.4312 IMPROVE LUBRICATION PRACTICES Savings:
$10,224
Cost:
$8,000
$10,224 238,570 - - - - $10,224
238,570
kWh
-
-
MMBtu
-
-
$
06: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS Savings:
$4,321
Cost:
$1,020
$4,321 100,821 - - - - $4,321
100,821
kWh
-
-
MMBtu
-
-
$
07: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$1,984
Cost:
$50
$1,984 46,307 - - - - $1,984
46,307
kWh
-
-
MMBtu
-
-
$
08: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT Savings:
$998
Cost:
$450
- - $998 244 - - -
-
kWh
$998
244
MMBtu
-
-
$
09: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$468
Cost:
$400
$468 10,844 - - - - $468
10,844
kWh
-
-
MMBtu
-
-
$
10: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$484
Cost:
$400
$484 11,430 - - - - $484
11,430
kWh
-
-
MMBtu
-
-
$
TOTAL RECOMMENDED Savings:
$92,335
Cost:
$94,135
$41,551 577,081 $35,284 8,627 $15,500 - $41,551
577,081
kWh
$35,284
8,627
MMBtu
$15,500
-
$
TOTAL IMPLEMENTED Savings:
$75,513
Cost:
$85,135
$24,729 577,081 $35,284 8,627 $15,500 - $24,729
577,081
kWh
$35,284
8,627
MMBtu
$15,500
-
$
Savings
Cost
$ kWh $ MMBtu $ $
Electricity Usage Natural Gas Administrative Changes Electricity Usage Natural Gas Administrative Changes