Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Louisiana, Lafayette |
---|---|
Assessment Year | 2010 |
Principal Product | Wood products |
NAICS | 321912 - Cut Stock, Resawing Lumber, and Planing |
SIC | 2421 - Sawmills And Planing Mills, General |
Sales | $10,000,000-$50,000,000 |
# of Employees | 105 |
Plant Area (Sq.Ft.) | 450,000 |
Annual Production | 93,000,000 Pieces |
Production Hrs. Annual | 8,736 |
Location (State) | AR |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $4,519,176 | 71,646,400 | kWh | $0.06 |
Electricity Fees | $162,269 | - | $ | - |
Natural Gas | $4,856,640 | 701,760 | MMBtu | $6.92 |
TOTAL ENERGY COSTS | $9,538,085 | |||
RECOMMENDED SAVINGS* | $676,480 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $628,698 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Fees | Natural Gas | Electricity Usage | Electricity Fees | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | $ | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.2135 REPAIR AND ELIMINATE STEAM LEAKS |
Savings: $271,505 Cost: $2,920 |
- | - | - | - | $271,505 | 39,229 |
- - kWh |
- - $ |
$271,505 39,229 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2121 INCREASE AMOUNT OF CONDENSATE RETURNED |
Savings: $204,298 Cost: $966,460 |
- | - | - | - | $204,298 | 25,160 |
- - kWh |
- - $ |
$204,298 25,160 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $152,895 Cost: $42,400 |
$147,595 | 2,339,807 | $5,300 | - | - | - |
$147,595 2,339,807 kWh |
$5,300 - $ |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $31,760 Cost: $6,240 |
- | - | - | - | $31,760 | 4,589 |
- - kWh |
- - $ |
$31,760 4,589 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $5,510 Cost: $10,605 |
$5,319 | 84,315 | $191 | - | - | - |
$5,319 84,315 kWh |
$191 - $ |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $5,365 Cost: $1,950 |
$5,179 | 82,105 | $186 | - | - | - |
$5,179 82,105 kWh |
$186 - $ |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $3,388 Cost: $1,950 |
$3,271 | 51,854 | $117 | - | - | - |
$3,271 51,854 kWh |
$117 - $ |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $1,302 Cost: $150 |
$1,257 | 19,921 | $45 | - | - | - |
$1,257 19,921 kWh |
$45 - $ |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.6211 CONSERVE ENERGY BY EFFICIENT USE OF VENDING MACHINES |
Savings: $457 Cost: $623 |
$441 | 6,989 | $16 | - | - | - |
$441 6,989 kWh |
$16 - $ |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $676,480 Cost: $1,033,298 |
$163,062 | 2,584,991 | $5,855 | - | $507,563 | 68,978 | $163,062 2,584,991 kWh |
$5,855 - $ |
$507,563 68,978 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $628,698 Cost: $1,011,780 |
$147,595 | 2,339,807 | $5,300 | - | $475,803 | 64,389 | $147,595 2,339,807 kWh |
$5,300 - $ |
$475,803 64,389 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | $ | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Fees | Natural Gas | Electricity Usage | Electricity Fees | Natural Gas |