Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Loyola Marymount University |
---|---|
Assessment Year | 2005 |
Principal Product | air frame fasteners |
NAICS | 332721 - Precision Turned Product Manufacturing |
SIC | 3451 - Screw Machine Products |
Sales | $10,000,000-$50,000,000 |
# of Employees | 360 |
Plant Area (Sq.Ft.) | 124,000 |
Annual Production | 98,760,000 Pieces |
Production Hrs. Annual | 4,000 |
Location (State) | CA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $851,177 | 11,087,326 | kWh | $0.08 |
Electricity Demand | $384,949 | 28,692 | kW-months/year | $13.42 |
Electricity Fees | $149,429 | - | $ | - |
TOTAL ENERGY COSTS | $1,385,555 | |||
RECOMMENDED SAVINGS* | $237,325 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $22,880 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Primary Product | Electricity Usage | Electricity Demand | Primary Product | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $12,671 Cost: - |
$8,210 | 101,568 | $4,461 | 305 | - | - |
$8,210 101,568 kWh |
$4,461 305 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 4.122 DEVELOP STANDARD PROCEDURES TO IMPROVE INTERNAL YIELDS |
Savings: $200,454 Cost: $75,500 |
- | - | - | - | $200,454 | - |
- - kWh |
- - kW-months/year |
$200,454 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $1,320 Cost: $1,178 |
$658 | 8,140 | $662 | 46 | - | - |
$658 8,140 kWh |
$662 46 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $10,490 Cost: $18,642 |
$6,797 | 84,084 | $3,693 | 252 | - | - |
$6,797 84,084 kWh |
$3,693 252 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $12,390 Cost: $1,225 |
$8,029 | 99,320 | $4,361 | 298 | - | - |
$8,029 99,320 kWh |
$4,361 298 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $237,325 Cost: $96,545 |
$23,694 | 293,112 | $13,177 | 901 | $200,454 | - | $23,694 293,112 kWh |
$13,177 901 kW-months/year |
$200,454 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $22,880 Cost: $19,867 |
$14,826 | 183,404 | $8,054 | 550 | - | - | $14,826 183,404 kWh |
$8,054 550 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Primary Product | Electricity Usage | Electricity Demand | Primary Product |