Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Massachusetts
Assessment Year 2007
Principal Product Watch & Electronic Batteries, Hearing Aid Batteries
NAICS 335912 - Primary Battery Manufacturing
SIC 3692 - Primary Batteries, Dry And Wet
Sales $50,000,000-$100,000,000
# of Employees 209
Plant Area (Sq.Ft.) 300,000
Annual Production 225,000 Pieces
Production Hrs. Annual 6,240
Location (State) VT
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $657,447 10,865,141 kWh $0.06
Electricity Demand $320,789 20,372 kW-months/year $15.75
Fuel Oil #4 $512,848 41,099 MMBtu $12.48
TOTAL ENERGY COSTS $1,491,084
RECOMMENDED SAVINGS* $193,543 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $138,761
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Fuel Oil #4 Electricity Usage Electricity Demand Fuel Oil #4
$ kWh $ kW-months/year $ MMBtu
01: 2.2113 REPAIR OR REPLACE STEAM TRAPS Savings:
$62,300
Cost:
$24,500
- - - - $62,300 4,992 -
-
kWh
-
-
kW-months/year
$62,300
4,992
MMBtu
02: 2.7224 REDUCE SPACE CONDITIONING DURING NON-WORKING HOURS Savings:
$47,607
Cost:
$22,000
$13,550 223,600 - - $34,057 2,729 $13,550
223,600
kWh
-
-
kW-months/year
$34,057
2,729
MMBtu
03: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT Savings:
$24,012
Cost:
$50,000
- - - - $24,012 1,924 -
-
kWh
-
-
kW-months/year
$24,012
1,924
MMBtu
04: 2.2625 CHILL WATER TO THE HIGHEST TEMPERATURE POSSIBLE Savings:
$14,298
Cost:
$11,500
$1,120 18,479 - - $13,178 1,056 $1,120
18,479
kWh
-
-
kW-months/year
$13,178
1,056
MMBtu
05: 2.1116 IMPROVE COMBUSTION CONTROL CAPABILITY Savings:
$12,255
Cost:
$75,000
- - - - $12,255 982 -
-
kWh
-
-
kW-months/year
$12,255
982
MMBtu
06: 2.3191 USE DEMAND CONTROLLER OR LOAD SHEDDER Savings:
$11,448
Cost:
$2,500
- - $11,448 1,812 - - -
-
kWh
$11,448
1,812
kW-months/year
-
-
MMBtu
07: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$4,741
Cost:
-
$3,233 53,352 $1,508 103 - - $3,233
53,352
kWh
$1,508
103
kW-months/year
-
-
MMBtu
08: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT Savings:
$4,655
Cost:
$4,000
- - - - $4,655 373 -
-
kWh
-
-
kW-months/year
$4,655
373
MMBtu
09: 2.7241 INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT Savings:
$4,605
Cost:
$1,000
$4,605 76,000 - - - - $4,605
76,000
kWh
-
-
kW-months/year
-
-
MMBtu
10: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$4,007
Cost:
$12,000
$4,007 66,120 - - - - $4,007
66,120
kWh
-
-
kW-months/year
-
-
MMBtu
11: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$2,570
Cost:
$15,700
$1,750 28,872 $820 56 - - $1,750
28,872
kWh
$820
56
kW-months/year
-
-
MMBtu
12: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$1,045
Cost:
$5,670
$430 7,151 $615 42 - - $430
7,151
kWh
$615
42
kW-months/year
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$193,543
Cost:
$223,870
$28,695 473,574 $14,391 2,013 $150,457 12,056 $28,695
473,574
kWh
$14,391
2,013
kW-months/year
$150,457
12,056
MMBtu
TOTAL IMPLEMENTED Savings:
$138,761
Cost:
$185,170
$8,790 145,102 $13,571 1,957 $116,400 9,327 $8,790
145,102
kWh
$13,571
1,957
kW-months/year
$116,400
9,327
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ MMBtu
Electricity Usage Electricity Demand Fuel Oil #4 Electricity Usage Electricity Demand Fuel Oil #4