Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Massachusetts
Assessment Year 2022
Principal Product Electronic components and circuits
NAICS 334419 - Other Electronic Component Manufacturing
SIC 3671 - Electron Tubes
Sales $50,000,000-$100,000,000
# of Employees 353
Plant Area (Sq.Ft.) 334,400
Annual Production 5,281 Units
Production Hrs. Annual 8,592
Location (State) MA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $1,263,570 9,093,600 kWh $0.14
Electricity Demand $111,007 19,272 kW-months/year $5.76
Electricity Fees $44,507 - $ -
Natural Gas $183,372 16,551 MMBtu $11.08
TOTAL ENERGY COSTS $1,644,919
RECOMMENDED SAVINGS* $512,535 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $119,775
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Water Usage Water Disposal Administrative Changes Electricity Usage Electricity Demand Natural Gas Water Usage Water Disposal Administrative Changes
$ kWh $ kW-months/year $ MMBtu $ Tgal $ Tgal $ $
01: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY Savings:
$247,461
Cost:
$2,531,558
$156,964 1,129,236 - - - - - - - - $90,497 - $156,964
1,129,236
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
Tgal
-
-
Tgal
$90,497
-
$
02: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$60,697
Cost:
$25,920
$38,373 276,068 - - $22,324 2,015 - - - - - - $38,373
276,068
kWh
-
-
kW-months/year
$22,324
2,015
MMBtu
-
-
Tgal
-
-
Tgal
-
-
$
03: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$42,489
Cost:
$9,040
$20,165 145,076 - - $22,324 2,015 - - - - - - $20,165
145,076
kWh
-
-
kW-months/year
$22,324
2,015
MMBtu
-
-
Tgal
-
-
Tgal
-
-
$
04: 3.3132 USE REVERSE OSMOSIS TO CONCENTRATE MATERIAL Savings:
$42,140
Cost:
$270,000
$(-4,980) (-35,829) $(-288) (-50) - - $15,562 3,855 $31,846 3,855 - - $(-4,980)
(-35,829)
kWh
$(-288)
(-50)
kW-months/year
-
-
MMBtu
$15,562
3,855
Tgal
$31,846
3,855
Tgal
-
-
$
05: 2.8121 APPLY FOR TAX-FREE STATUS FOR ENERGY PURCHASES Savings:
$41,831
Cost:
$1,000
- - - - - - - - - - $41,831 - -
-
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
Tgal
-
-
Tgal
$41,831
-
$
06: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$39,808
Cost:
$21,525
$37,671 271,013 $2,137 371 - - - - - - - - $37,671
271,013
kWh
$2,137
371
kW-months/year
-
-
MMBtu
-
-
Tgal
-
-
Tgal
-
-
$
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$34,657
Cost:
$42,058
$32,762 235,696 $1,895 329 - - - - - - - - $32,762
235,696
kWh
$1,895
329
kW-months/year
-
-
MMBtu
-
-
Tgal
-
-
Tgal
-
-
$
08: 2.2614 USE COOLING TOWER OR ECONOMIZER TO REPLACE CHILLER COOLING Savings:
$2,654
Cost:
$15,630
$2,383 17,141 $271 47 - - - - - - - - $2,383
17,141
kWh
$271
47
kW-months/year
-
-
MMBtu
-
-
Tgal
-
-
Tgal
-
-
$
09: 2.2123 INSULATE FEEDWATER TANK Savings:
$798
Cost:
$1,376
- - - - $798 72 - - - - - - -
-
kWh
-
-
kW-months/year
$798
72
MMBtu
-
-
Tgal
-
-
Tgal
-
-
$
TOTAL RECOMMENDED Savings:
$512,535
Cost:
$2,918,107
$283,338 2,038,401 $4,015 697 $45,446 4,102 $15,562 3,855 $31,846 3,855 $132,328 - $283,338
2,038,401
kWh
$4,015
697
kW-months/year
$45,446
4,102
MMBtu
$15,562
3,855
Tgal
$31,846
3,855
Tgal
$132,328
-
$
TOTAL IMPLEMENTED Savings:
$119,775
Cost:
$53,474
$52,927 380,772 $1,895 329 $23,122 2,087 - - - - $41,831 - $52,927
380,772
kWh
$1,895
329
kW-months/year
$23,122
2,087
MMBtu
-
-
Tgal
-
-
Tgal
$41,831
-
$
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ Tgal $ Tgal $ $
Electricity Usage Electricity Demand Natural Gas Water Usage Water Disposal Administrative Changes Electricity Usage Electricity Demand Natural Gas Water Usage Water Disposal Administrative Changes