Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Miami |
---|---|
Assessment Year | 2017 |
Principal Product | Surgical tools |
NAICS | 339112 - Surgical and Medical Instrument Manufacturing |
SIC | 3841 - Surgical And Medical Instruments |
Sales | $10,000,000-$50,000,000 |
# of Employees | 150 |
Plant Area (Sq.Ft.) | 66,000 |
Annual Production | 84,000,000 Units |
Production Hrs. Annual | 8,568 |
Location (State) | PR |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $581,299 | 3,689,275 | kWh | $0.16 |
Electricity Demand | $82,454 | 10,572 | kW-months/year | $7.80 |
Electricity Fees | $8,090 | - | $ | - |
TOTAL ENERGY COSTS | $671,843 | |||
RECOMMENDED SAVINGS* | $182,536 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $78,765 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Administrative Changes | Electricity Usage | Electricity Demand | Electricity Fees | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.2628 UTILIZE A LESS EXPENSIVE COOLING METHOD |
Savings: $94,097 Cost: $134,000 |
$83,336 | 527,446 | $5,761 | 739 | - | - | $5,000 | - |
$83,336 527,446 kWh |
$5,761 739 kW-months/year |
- - $ |
$5,000 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7425 CLEAN OR COLOR ROOF TO REDUCE SOLAR LOAD |
Savings: $28,637 Cost: $15,056 |
$26,785 | 169,528 | $1,852 | 237 | - | - | - | - |
$26,785 169,528 kWh |
$1,852 237 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $28,032 Cost: $41,300 |
- | - | $28,032 | 3,602 | - | - | - | - |
- - kWh |
$28,032 3,602 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $8,387 Cost: $8,923 |
$7,856 | 49,722 | $531 | 68 | - | - | - | - |
$7,856 49,722 kWh |
$531 68 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.8112 COMBINE UTILITY METERS |
Savings: $7,245 Cost: $100 |
- | - | $4,845 | 600 | $2,400 | - | - | - |
- - kWh |
$4,845 600 kW-months/year |
$2,400 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $5,467 Cost: $4,900 |
$5,467 | 34,602 | - | - | - | - | - | - |
$5,467 34,602 kWh |
- - kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS |
Savings: $3,663 Cost: $1,478 |
$3,430 | 21,706 | $233 | 30 | - | - | - | - |
$3,430 21,706 kWh |
$233 30 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $3,528 Cost: $1,000 |
$3,528 | 22,327 | - | - | - | - | - | - |
$3,528 22,327 kWh |
- - kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS |
Savings: $1,760 Cost: $250 |
$1,645 | 10,410 | $115 | 15 | - | - | - | - |
$1,645 10,410 kWh |
$115 15 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS |
Savings: $1,051 Cost: $1,722 |
$983 | 6,221 | $68 | 9 | - | - | - | - |
$983 6,221 kWh |
$68 9 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.3191 USE DEMAND CONTROLLER OR LOAD SHEDDER |
Savings: $670 Cost: $100 |
- | - | - | - | $670 | - | - | - |
- - kWh |
- - kW-months/year |
$670 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $182,536 Cost: $208,829 |
$133,030 | 841,962 | $41,437 | 5,299 | $3,070 | - | $5,000 | - | $133,030 841,962 kWh |
$41,437 5,299 kW-months/year |
$3,070 - $ |
$5,000 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $78,765 Cost: $74,379 |
$48,049 | 304,106 | $30,716 | 3,946 | - | - | - | - | $48,049 304,106 kWh |
$30,716 3,946 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Administrative Changes | Electricity Usage | Electricity Demand | Electricity Fees | Administrative Changes |