Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center North Carolina State
Assessment Year 1994
Principal Product Wood / Metal Kitchen Furniture
NAICS n/a
SIC 2514 - Metal Household Furniture
Sales $10,000,000-$50,000,000
# of Employees 400
Plant Area (Sq.Ft.) 445,000
Annual Production 0 Units
Production Hrs. Annual 2,000
Location (State) NC
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $261,008 4,615,475 kWh $0.06
LPG $67,709 8,462 MMBtu $8.00
Fuel Oil #2 $30,398 6,305 MMBtu $4.82
TOTAL ENERGY COSTS $359,115
RECOMMENDED SAVINGS* $31,462 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $9,175
#|Description Savings
Cost
Status Electricity Usage Fuel Oil #2 Electricity Usage Fuel Oil #2
$ kWh $ MMBtu
01: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$5,391
Cost:
$1,620
$5,391 94,666 - - $5,391
94,666
kWh
-
-
MMBtu
02: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$1,132
Cost:
$700
$1,132 19,930 - - $1,132
19,930
kWh
-
-
MMBtu
03: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT Savings:
$1,131
Cost:
$500
- - $1,131 141 -
-
kWh
$1,131
141
MMBtu
04: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$824
Cost:
-
$824 14,361 - - $824
14,361
kWh
-
-
MMBtu
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$3,711
Cost:
$1,085
$3,711 65,064 - - $3,711
65,064
kWh
-
-
MMBtu
06: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS Savings:
$664
Cost:
$820
$664 11,723 - - $664
11,723
kWh
-
-
MMBtu
07: 2.7243 IMPROVE AIR CIRCULATION WITH DESTRATIFICATION FANS / OTHER METHODS Savings:
$7,987
Cost:
$17,200
- - $7,987 1,735 -
-
kWh
$7,987
1,735
MMBtu
08: 2.7241 INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT Savings:
$1,639
Cost:
$2,000
$1,639 28,722 - - $1,639
28,722
kWh
-
-
MMBtu
09: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$2,960
Cost:
$9,280
$2,960 51,876 - - $2,960
51,876
kWh
-
-
MMBtu
10: 2.2443 RE-USE OR RECYCLE HOT OR COLD PROCESS EXHAUST AIR Savings:
$6,023
Cost:
$3,650
- - $6,023 768 -
-
kWh
$6,023
768
MMBtu
TOTAL RECOMMENDED Savings:
$31,462
Cost:
$36,855
$16,321 286,342 $15,141 2,644 $16,321
286,342
kWh
$15,141
2,644
MMBtu
TOTAL IMPLEMENTED Savings:
$9,175
Cost:
$10,900
$9,175 160,903 - - $9,175
160,903
kWh
-
-
MMBtu
Savings
Cost
$ kWh $ MMBtu
Electricity Usage Fuel Oil #2 Electricity Usage Fuel Oil #2