Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | North Carolina State |
---|---|
Assessment Year | 2003 |
Principal Product | Vinyl siding |
NAICS | 326111 - Plastics Bag and Pouch Manufacturing |
SIC | 3080 - |
Sales | $50,000,000-$100,000,000 |
# of Employees | 250 |
Plant Area (Sq.Ft.) | 443,000 |
Annual Production | 2,400 Thousand Feet |
Production Hrs. Annual | 8,400 |
Location (State) | NC |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $619,107 | 23,378,544 | kWh | $0.03 |
Electricity Demand | $341,491 | 37,404 | kW-months/year | $9.13 |
Electricity Fees | $32,246 | - | $ | - |
Natural Gas | $38,462 | 5,538 | MMBtu | $6.95 |
TOTAL ENERGY COSTS | $1,031,306 | |||
RECOMMENDED SAVINGS* | $54,350 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $23,524 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Water Consumption | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Water Consumption | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | Tgal | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $7,357 Cost: $1,650 |
$5,073 | 192,144 | $2,284 | 275 | - | - | - | - | - | - |
$5,073 192,144 kWh |
$2,284 275 kW-months/year |
- - MMBtu |
- - $ |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4151 DEVELOP A REPAIR/REPLACE POLICY |
Savings: $3,711 Cost: $5,940 |
$2,560 | 96,983 | $1,151 | 138 | - | - | - | - | - | - |
$2,560 96,983 kWh |
$1,151 138 kW-months/year |
- - MMBtu |
- - $ |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.6221 USE MOST EFFICIENT EQUIPMENT AT IT'S MAXIMUM CAPACITY AND LESS EFFICIENT EQUIPMENT ONLY WHEN NECESSARY |
Savings: $6,070 Cost: - |
$(-423) | (-16,000) | $(-190) | (-23) | $6,783 | 975 | $(-100) | - | - | - |
$(-423) (-16,000) kWh |
$(-190) (-23) kW-months/year |
$6,783 975 MMBtu |
$(-100) - $ |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $6,905 Cost: $50 |
$4,763 | 180,432 | $2,142 | 258 | - | - | - | - | - | - |
$4,763 180,432 kWh |
$2,142 258 kW-months/year |
- - MMBtu |
- - $ |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $4,513 Cost: $2,750 |
$2,216 | 83,950 | $2,297 | 276 | - | - | - | - | - | - |
$2,216 83,950 kWh |
$2,297 276 kW-months/year |
- - MMBtu |
- - $ |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7131 ADD AREA LIGHTING SWITCHES |
Savings: $3,306 Cost: $1,200 |
$2,203 | 83,462 | $1,103 | 132 | - | - | - | - | - | - |
$2,203 83,462 kWh |
$1,103 132 kW-months/year |
- - MMBtu |
- - $ |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $887 Cost: $862 |
$613 | 23,212 | $274 | 33 | - | - | - | - | - | - |
$613 23,212 kWh |
$274 33 kW-months/year |
- - MMBtu |
- - $ |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $1,879 Cost: $1,740 |
$1,296 | 49,083 | $583 | 70 | - | - | - | - | - | - |
$1,296 49,083 kWh |
$583 70 kW-months/year |
- - MMBtu |
- - $ |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.2614 USE COOLING TOWER OR ECONOMIZER TO REPLACE CHILLER COOLING |
Savings: $13,286 Cost: $10,000 |
$13,286 | 606,375 | - | - | - | - | - | - | - | - |
$13,286 606,375 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.2625 CHILL WATER TO THE HIGHEST TEMPERATURE POSSIBLE |
Savings: $2,785 Cost: $12,240 |
$1,920 | 72,744 | $865 | 104 | - | - | - | - | - | - |
$1,920 72,744 kWh |
$865 104 kW-months/year |
- - MMBtu |
- - $ |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.3113 MAKE ICE DURING OFF PEAK HOURS FOR COOLING |
Savings: $3,651 Cost: $38,000 |
$2,084 | 42,960 | $2,897 | 348 | - | - | - | - | $(-1,330) | - |
$2,084 42,960 kWh |
$2,897 348 kW-months/year |
- - MMBtu |
- - $ |
$(-1,330) - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $54,350 Cost: $74,432 |
$35,591 | 1,415,345 | $13,406 | 1,611 | $6,783 | 975 | $(-100) | - | $(-1,330) | - | $35,591 1,415,345 kWh |
$13,406 1,611 kW-months/year |
$6,783 975 MMBtu |
$(-100) - $ |
$(-1,330) - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $23,524 Cost: $22,482 |
$16,225 | 614,598 | $7,299 | 878 | - | - | - | - | - | - | $16,225 614,598 kWh |
$7,299 878 kW-months/year |
- - MMBtu |
- - $ |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | Tgal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Water Consumption | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Water Consumption |