IAC Center | North Carolina State |
---|---|
Assessment Year | 2014 |
Principal Product | Fabric for lingerie |
NAICS | 315190 - Other Apparel Knitting Mills |
SIC | 2254 - Knit Underwear Mills |
Sales | $50,000,000-$100,000,000 |
# of Employees | 247 |
Plant Area (Sq.Ft.) | 175,000 |
Annual Production | 300,000,000 Pounds |
Production Hrs. Annual | 8,400 |
Location (State) | VA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $497,677 | 13,168,800 | kWh | $0.04 |
Electricity Demand | $463,942 | 27,501 | kW-months/year | $16.87 |
Electricity Fees | $3,480 | - | $ | - |
LPG | $971,857 | 53,781 | MMBtu | $18.07 |
TOTAL ENERGY COSTS | $1,936,956 | |||
RECOMMENDED SAVINGS* | $641,448 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $455,314 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | LPG | Water Disposal | Ancillary Material Cost | Electricity Usage | Electricity Demand | LPG | Water Disposal | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $123,080 Cost: $103,307 |
$10,699 | 283,049 | $6,851 | 406 | $105,530 | 5,840 | - | - | - | - |
$10,699 283,049 kWh |
$6,851 406 kW-months/year |
$105,530 5,840 MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES |
Savings: $364,896 Cost: $1,350,000 |
- | - | - | - | $69,410 | 3,841 | $22,182 | 9,320 | $273,304 | - |
- - kWh |
- - kW-months/year |
$69,410 3,841 MMBtu |
$22,182 9,320 Tgal |
$273,304 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.3131 RESCHEDULE PLANT OPERATIONS OR REDUCE LOAD TO AVOID PEAKS |
Savings: $57,030 Cost: $40,000 |
- | - | $57,030 | 3,856 | - | - | - | - | - | - |
- - kWh |
$57,030 3,856 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT |
Savings: $21,678 Cost: $40,000 |
- | - | - | - | $21,678 | 1,200 | - | - | - | - |
- - kWh |
- - kW-months/year |
$21,678 1,200 MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2427 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT INCOMING FLUIDS |
Savings: $41,376 Cost: $72,000 |
$14,311 | 378,600 | $27,065 | 1,604 | - | - | - | - | - | - |
$14,311 378,600 kWh |
$27,065 1,604 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $2,043 Cost: $5,100 |
$1,080 | 28,560 | $963 | 57 | - | - | - | - | - | - |
$1,080 28,560 kWh |
$963 57 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $26,870 Cost: $102,717 |
$11,679 | 308,977 | $9,298 | 551 | - | - | - | - | $5,893 | - |
$11,679 308,977 kWh |
$9,298 551 kW-months/year |
- - MMBtu |
- - Tgal |
$5,893 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $2,313 Cost: $650 |
$2,313 | 61,182 | - | - | - | - | - | - | - | - |
$2,313 61,182 kWh |
- - kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4151 DEVELOP A REPAIR/REPLACE POLICY |
Savings: $2,162 Cost: $4,256 |
$1,142 | 30,221 | $1,020 | 60 | - | - | - | - | - | - |
$1,142 30,221 kWh |
$1,020 60 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $641,448 Cost: $1,718,030 |
$41,224 | 1,090,589 | $102,227 | 6,534 | $196,618 | 10,881 | $22,182 | 9,320 | $279,197 | - | $41,224 1,090,589 kWh |
$102,227 6,534 kW-months/year |
$196,618 10,881 MMBtu |
$22,182 9,320 Tgal |
$279,197 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $455,314 Cost: $1,502,723 |
$16,214 | 428,940 | $68,311 | 4,524 | $69,410 | 3,841 | $22,182 | 9,320 | $279,197 | - | $16,214 428,940 kWh |
$68,311 4,524 kW-months/year |
$69,410 3,841 MMBtu |
$22,182 9,320 Tgal |
$279,197 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | LPG | Water Disposal | Ancillary Material Cost | Electricity Usage | Electricity Demand | LPG | Water Disposal | Ancillary Material Cost |