Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Nevada |
---|---|
Assessment Year | 1997 |
Principal Product | Precision Flow Regulating Equipment |
NAICS | n/a |
SIC | 3549 - Metalworking Machinery, Nec |
Sales | $10,000,000-$50,000,000 |
# of Employees | 128 |
Plant Area (Sq.Ft.) | 43,000 |
Annual Production | 80,000 Pieces |
Production Hrs. Annual | 4,940 |
Location (State) | NV |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $37,483 | 859,027 | kWh | $0.04 |
Electricity Demand | $24,082 | 2,595 | kW-months/year | $9.28 |
Electricity Fees | $1,231 | - | $ | - |
Natural Gas | $5,150 | 976 | MMBtu | $5.28 |
TOTAL ENERGY COSTS | $139,063 | |||
RECOMMENDED SAVINGS* | $80,486 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $68,175 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Other Liquid (haz) | Solid Waste (non-haz) | Electricity Usage | Electricity Demand | Natural Gas | Other Liquid (haz) | Solid Waste (non-haz) | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | gal | $ | lb | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $458 Cost: $300 |
$458 | 10,551 | - | - | - | - | - | - | - | - |
$458 10,551 kWh |
- - kW-months/year |
- - MMBtu |
- - gal |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.3191 USE DEMAND CONTROLLER OR LOAD SHEDDER |
Savings: $426 Cost: $147 |
$100 | 2,345 | $326 | 35 | - | - | - | - | - | - |
$100 2,345 kWh |
$326 35 kW-months/year |
- - MMBtu |
- - gal |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $1,377 Cost: $850 |
- | - | - | - | $1,377 | 281 | - | - | - | - |
- - kWh |
- - kW-months/year |
$1,377 281 MMBtu |
- - gal |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $159 Cost: $150 |
$159 | 3,517 | - | - | - | - | - | - | - | - |
$159 3,517 kWh |
- - kW-months/year |
- - MMBtu |
- - gal |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $396 Cost: $50 |
$396 | 9,086 | - | - | - | - | - | - | - | - |
$396 9,086 kWh |
- - kW-months/year |
- - MMBtu |
- - gal |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $4,549 Cost: $885 |
$2,949 | 67,116 | $1,600 | 173 | - | - | - | - | - | - |
$2,949 67,116 kWh |
$1,600 173 kW-months/year |
- - MMBtu |
- - gal |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $5,633 Cost: $513 |
$3,725 | 84,701 | $1,908 | 206 | - | - | - | - | - | - |
$3,725 84,701 kWh |
$1,908 206 kW-months/year |
- - MMBtu |
- - gal |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $326 Cost: $164 |
$248 | 5,569 | $78 | 8 | - | - | - | - | - | - |
$248 5,569 kWh |
$78 8 kW-months/year |
- - MMBtu |
- - gal |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $412 Cost: $258 |
$265 | 6,155 | $147 | 16 | - | - | - | - | - | - |
$265 6,155 kWh |
$147 16 kW-months/year |
- - MMBtu |
- - gal |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 3.7197 USE ULTRASONIC CLEANING |
Savings: $65,000 Cost: $16,200 |
- | - | - | - | - | - | $65,000 | 1,490 | - | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$65,000 1,490 gal |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 3.5315 LEASE / PURCHASE BALER; SELL CARDBOARD TO RECYCLER |
Savings: $1,750 Cost: $500 |
- | - | - | - | - | - | - | - | $1,750 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
- - gal |
$1,750 - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $80,486 Cost: $20,017 |
$8,300 | 189,040 | $4,059 | 438 | $1,377 | 281 | $65,000 | 1,490 | $1,750 | - | $8,300 189,040 kWh |
$4,059 438 kW-months/year |
$1,377 281 MMBtu |
$65,000 1,490 gal |
$1,750 - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $68,175 Cost: $17,458 |
$1,278 | 29,309 | $147 | 16 | - | - | $65,000 | 1,490 | $1,750 | - | $1,278 29,309 kWh |
$147 16 kW-months/year |
- - MMBtu |
$65,000 1,490 gal |
$1,750 - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | gal | $ | lb | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Other Liquid (haz) | Solid Waste (non-haz) | Electricity Usage | Electricity Demand | Natural Gas | Other Liquid (haz) | Solid Waste (non-haz) |