Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Old Dominion Univ. |
---|---|
Assessment Year | 1996 |
Principal Product | Softboard sheathing |
NAICS | n/a |
SIC | 2499 - Wood Products, Nec |
Sales | $10,000,000-$50,000,000 |
# of Employees | 122 |
Plant Area (Sq.Ft.) | 200,000 |
Annual Production | 240,000 Thousand Feet |
Production Hrs. Annual | 8,568 |
Location (State) | VA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $990,943 | 58,804,807 | kWh | $0.02 |
Electricity Demand | $1,389,833 | 224,337 | kW-months/year | $6.20 |
Electricity Fees | $86,122 | - | $ | - |
Coal | $536,369 | 489,188 | MMBtu | $1.10 |
TOTAL ENERGY COSTS | $3,010,611 | |||
RECOMMENDED SAVINGS* | $472,755 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Solid Waste (non-haz) | Personnel Changes | Primary Product | Electricity Usage | Electricity Demand | Solid Waste (non-haz) | Personnel Changes | Primary Product | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | lb | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $5,023 Cost: $11,843 |
$3,324 | 196,659 | $1,699 | 274 | - | - | - | - | - | - |
$3,324 196,659 kWh |
$1,699 274 kW-months/year |
- - lb |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 4.114 ADD/MODIFY EQUIPMENT TO IMPROVE DRYING PROCESS |
Savings: $308,827 Cost: $235,200 |
$(-113,522) | (-6,717,468) | $(-55,651) | (-8,976) | - | - | $(-2,000) | - | $480,000 | - |
$(-113,522) (-6,717,468) kWh |
$(-55,651) (-8,976) kW-months/year |
- - lb |
$(-2,000) - $ |
$480,000 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $13,695 Cost: $24,130 |
$8,266 | 489,156 | $5,429 | 876 | - | - | - | - | - | - |
$8,266 489,156 kWh |
$5,429 876 kW-months/year |
- - lb |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7132 INSTALL TIMERS ON LIGHT SWITCHES IN LITTLE USED AREAS |
Savings: $3,454 Cost: $639 |
$3,454 | 204,279 | - | - | - | - | - | - | - | - |
$3,454 204,279 kWh |
- - kW-months/year |
- - lb |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.3134 SHIFT FROM DAYTIME TO NIGHTTIME OPERATION |
Savings: $124,620 Cost: $208,110 |
- | - | $124,620 | 20,100 | - | - | - | - | - | - |
- - kWh |
$124,620 20,100 kW-months/year |
- - lb |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 3.5313 INCREASE AMOUNT OF WASTE RECOVERED FOR RESALE |
Savings: $17,136 Cost: - |
- | - | - | - | $17,136 | 1,713,600 | - | - | - | - |
- - kWh |
- - kW-months/year |
$17,136 1,713,600 lb |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $472,755 Cost: $479,922 |
$(-98,478) | (-5,827,374) | $76,097 | 12,274 | $17,136 | 1,713,600 | $(-2,000) | - | $480,000 | - | $(-98,478) (-5,827,374) kWh |
$76,097 12,274 kW-months/year |
$17,136 1,713,600 lb |
$(-2,000) - $ |
$480,000 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - lb |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | lb | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Solid Waste (non-haz) | Personnel Changes | Primary Product | Electricity Usage | Electricity Demand | Solid Waste (non-haz) | Personnel Changes | Primary Product |