IAC logo
IAC Assessment: SD0607
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: SD0607
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center San Diego State University
Assessment Year 2021
Principal Product Flour
NAICS 311211 - Flour Milling
SIC 2041 - Flour And Other Grain Mill Products
Sales $50,000,000-$100,000,000
# of Employees 41
Plant Area (Sq.Ft.) 80,000
Annual Production 214,800 Tons
Production Hrs. Annual 8,592
Location (State) CA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $1,375,636 13,576,357 kWh $0.10
Electricity Demand $696,959 28,691 kW-months/year $24.29
Electricity Fees $181,724 - $ -
TOTAL ENERGY COSTS $2,254,319
RECOMMENDED SAVINGS* $66,386 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand One-time Revenue or Avoided Cost Electricity Usage Electricity Demand One-time Revenue or Avoided Cost
$ kWh $ kW-months/year $ $
01: 2.3132 RECHARGE BATTERIES ON DURING OFF-PEAK DEMAND PERIODS Savings:
$26,888
Cost:
$500
$7,604 423,561 $19,284 912 - - $7,604
423,561
kWh
$19,284
912
kW-months/year
-
-
$
02: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL Savings:
$17,809
Cost:
$38,800
$14,230 140,491 $3,579 147 - - $14,230
140,491
kWh
$3,579
147
kW-months/year
-
-
$
03: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$13,885
Cost:
$2,100
$11,893 117,404 $1,992 82 - - $11,893
117,404
kWh
$1,992
82
kW-months/year
-
-
$
04: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$2,753
Cost:
$568
$2,061 20,435 $692 29 - - $2,061
20,435
kWh
$692
29
kW-months/year
-
-
$
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$3,289
Cost:
$2,741
$2,387 23,573 $799 33 $103 - $2,387
23,573
kWh
$799
33
kW-months/year
$103
-
$
06: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS Savings:
$794
Cost:
$760
$595 5,877 $199 8 - - $595
5,877
kWh
$199
8
kW-months/year
-
-
$
07: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$481
Cost:
$706
$413 4,077 $68 3 - - $413
4,077
kWh
$68
3
kW-months/year
-
-
$
08: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$487
Cost:
$540
$365 3,599 $122 5 - - $365
3,599
kWh
$122
5
kW-months/year
-
-
$
TOTAL RECOMMENDED Savings:
$66,386
Cost:
$46,715
$39,548 739,017 $26,735 1,219 $103 - $39,548
739,017
kWh
$26,735
1,219
kW-months/year
$103
-
$
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - -
-
kWh
-
-
kW-months/year
-
-
$
Savings
Cost
$ kWh $ kW-months/year $ $
Electricity Usage Electricity Demand One-time Revenue or Avoided Cost Electricity Usage Electricity Demand One-time Revenue or Avoided Cost