Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center San Francisco State University
Assessment Year 1995
Principal Product Tofu, Pasta Products
NAICS n/a
SIC 2098 - Macaroni And Spaghetti
Sales $10,000,000-$50,000,000
# of Employees 90
Plant Area (Sq.Ft.) 40,000
Annual Production 1,500,000 Units
Production Hrs. Annual 2,990
Location (State) CA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $149,592 1,315,358 kWh $0.11
Natural Gas $73,224 11,202 MMBtu $6.54
TOTAL ENERGY COSTS $222,816
RECOMMENDED SAVINGS* $23,360 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $17,924
#|Description Savings
Cost
Status Electricity Usage Natural Gas Water Disposal Electricity Usage Natural Gas Water Disposal
$ kWh $ MMBtu $ Tgal
01: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$602
Cost:
$610
$602 5,862 - - - - $602
5,862
kWh
-
-
MMBtu
-
-
Tgal
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$3,041
Cost:
$9,983
$3,041 28,429 - - - - $3,041
28,429
kWh
-
-
MMBtu
-
-
Tgal
03: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$2,395
Cost:
$4,330
$2,395 22,567 - - - - $2,395
22,567
kWh
-
-
MMBtu
-
-
Tgal
04: 2.1243 USE HEAT FROM BOILER BLOWDOWN TO PREHEAT BOILER FEED WATER Savings:
$5,535
Cost:
$14,820
- - $5,535 846 - - -
-
kWh
$5,535
846
MMBtu
-
-
Tgal
05: 2.2511 INSULATE BARE EQUIPMENT Savings:
$1,695
Cost:
$1,918
- - $1,695 259 - - -
-
kWh
$1,695
259
MMBtu
-
-
Tgal
06: 2.4314 USE SYNTHETIC LUBRICANT Savings:
$421
Cost:
$758
$421 3,810 - - - - $421
3,810
kWh
-
-
MMBtu
-
-
Tgal
07: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$1,114
Cost:
$40
$1,114 10,551 - - - - $1,114
10,551
kWh
-
-
MMBtu
-
-
Tgal
08: 2.2123 INSULATE FEEDWATER TANK Savings:
$307
Cost:
$702
- - $307 51 - - -
-
kWh
$307
51
MMBtu
-
-
Tgal
09: 2.2121 INCREASE AMOUNT OF CONDENSATE RETURNED Savings:
$8,250
Cost:
$1,620
- - $4,248 650 $4,002 536,126 -
-
kWh
$4,248
650
MMBtu
$4,002
536,126
Tgal
TOTAL RECOMMENDED Savings:
$23,360
Cost:
$34,781
$7,573 71,219 $11,785 1,806 $4,002 536,126 $7,573
71,219
kWh
$11,785
1,806
MMBtu
$4,002
536,126
Tgal
TOTAL IMPLEMENTED Savings:
$17,924
Cost:
$20,468
$2,137 20,223 $11,785 1,806 $4,002 536,126 $2,137
20,223
kWh
$11,785
1,806
MMBtu
$4,002
536,126
Tgal
Savings
Cost
$ kWh $ MMBtu $ Tgal
Electricity Usage Natural Gas Water Disposal Electricity Usage Natural Gas Water Disposal