Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center San Francisco State University
Assessment Year 1998
Principal Product Applesauce,Applejuice,and Apple Vinegar
NAICS n/a
SIC 2033 - Canned Fruits And Vegetables
Sales $5,000,000-$10,000,000
# of Employees 0
Plant Area (Sq.Ft.) 100,000
Annual Production 7,630 Tons
Production Hrs. Annual 3,120
Location (State) CA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $82,902 986,225 kWh $0.08
Electricity Demand $14,092 3,182 kW-months/year $4.43
Natural Gas $76,723 22,550 MMBtu $3.40
TOTAL ENERGY COSTS $184,029
RECOMMENDED SAVINGS* $9,801 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $6,120
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Solid Waste (non-haz) Electricity Usage Electricity Demand Natural Gas Solid Waste (non-haz)
$ kWh $ kW-months/year $ MMBtu $ lb
01: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$3,167
Cost:
$156
$2,602 31,067 $565 128 - - - - $2,602
31,067
kWh
$565
128
kW-months/year
-
-
MMBtu
-
-
lb
02: 2.7124 MAKE A PRACTICE OF TURNING OFF LIGHTS WHEN NOT NEEDED Savings:
$878
Cost:
-
$545 6,448 $333 75 - - - - $545
6,448
kWh
$333
75
kW-months/year
-
-
MMBtu
-
-
lb
03: 2.2121 INCREASE AMOUNT OF CONDENSATE RETURNED Savings:
$1,152
Cost:
$1,611
- - - - $1,152 339 - - -
-
kWh
-
-
kW-months/year
$1,152
339
MMBtu
-
-
lb
04: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$675
Cost:
$967
$517 6,155 $158 36 - - - - $517
6,155
kWh
$158
36
kW-months/year
-
-
MMBtu
-
-
lb
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$2,803
Cost:
$7,808
$2,281 27,257 $522 118 - - - - $2,281
27,257
kWh
$522
118
kW-months/year
-
-
MMBtu
-
-
lb
06: 2.1242 MINIMIZE BOILER BLOWDOWN WITH BETTER FEEDWATER TREATMENT Savings:
$610
Cost:
$3,500
- - - - $610 133 - - -
-
kWh
-
-
kW-months/year
$610
133
MMBtu
-
-
lb
07: 3.5315 LEASE / PURCHASE BALER; SELL CARDBOARD TO RECYCLER Savings:
$516
Cost:
-
- - - - - - $516 - -
-
kWh
-
-
kW-months/year
-
-
MMBtu
$516
-
lb
TOTAL RECOMMENDED Savings:
$9,801
Cost:
$14,042
$5,945 70,927 $1,578 357 $1,762 472 $516 - $5,945
70,927
kWh
$1,578
357
kW-months/year
$1,762
472
MMBtu
$516
-
lb
TOTAL IMPLEMENTED Savings:
$6,120
Cost:
$6,234
$3,119 37,222 $723 164 $1,762 472 $516 - $3,119
37,222
kWh
$723
164
kW-months/year
$1,762
472
MMBtu
$516
-
lb
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ lb
Electricity Usage Electricity Demand Natural Gas Solid Waste (non-haz) Electricity Usage Electricity Demand Natural Gas Solid Waste (non-haz)